Safety precautions for the frequency converter
•
This equipment is used in high-voltage installations. During operation, this equipment
contains rotating and live, bare parts. For this reason, it could cause severe injury or
significant material damage if the required covers are removed or have not been properly
maintained.
•
When the machines are used in non-industrial areas, the installation location must be
protected against unauthorized access (protective fencing, appropriate signs).
•
All connection procedures must be carried out with the cabinet de-energized. All the work
on the units must be carried out by trained personnel only. Death, serious injury, or
substantial material damage can result if these warnings are not taken into account.
•
Work on an open device must be carried out with extreme caution because external
supply voltages may be present. The power and control terminals may be live even when
the motor is not running.
Dangerously high voltage levels are still present in the cabinet up to five minutes after it
has been disconnected due to the DC link capacitors. For this reason, the cabinet should
not be opened until after a reasonable period of time has elapsed.
•
The operator is responsible for ensuring that the Power Module and other components
are installed and connected in accordance with the recognized technical rules in the
country of installation and applicable regional guidelines. Special attention should be paid
to cable dimensioning, fuses, grounding, shutdown, disconnection, and overcurrent
protection.
•
If an item of protecting gear trips in a branch circuit, a leakage current may have been
disconnected. To reduce the risk of fire or an electric shock, the current-carrying parts
and other components in the cabinet unit should be inspected and damaged parts
replaced. When an item of protective gear trips, the cause of tripping must be identified
and rectified.
•
The storage period should not exceed two years. If the device is stored for more than two
years, the DC link capacitors of the devices must be reformed during commissioning.
Consult your Service Centre for the reforming procedure.
Instruction book
96
2920 1804 00
Содержание CPF 175
Страница 1: ...CPF 175 CPVS 175 Instruction book ...
Страница 2: ......
Страница 7: ...11 Declaration of conformity 148 Instruction book 2920 1804 00 5 ...
Страница 15: ...2 2 Air and oil system Flow diagrams Flow diagram air cooled compressor Instruction book 2920 1804 00 13 ...
Страница 18: ...Flow diagram water cooled compressor with modulating control Instruction book 16 2920 1804 00 ...
Страница 33: ...Menu structure for fixed speed compressors Instruction book 2920 1804 00 31 ...
Страница 34: ...Menu structure for variable speed compressors Instruction book 32 2920 1804 00 ...
Страница 60: ...Fixed speed compressors Instruction book 58 2920 1804 00 ...
Страница 72: ...Fixed speed compressors Instruction book 70 2920 1804 00 ...
Страница 104: ...Electrical connections for IEC variable speed compressors Instruction book 102 2920 1804 00 ...
Страница 105: ...Electrical connections for CSA UL fixed speed compressors Instruction book 2920 1804 00 103 ...
Страница 151: ......
Страница 152: ...No 2920 1804 00 2012 08 ...