Reference
Description
(6)
Configuration of the action to be performed on the programmed date.
(7)
Refer to the definition of actions given below.
(8)
Scroll
(9)
Validation
(10)
Modification
(11)
Setting
(12)
Selection
The menu Weekly Program allows programming over a week, the starts and stops of the compressor as well
as the pressure regulation bands. For each day of the week, up to 6 programme steps can be defined. For each
of these steps, the time and type of the action to be performed can be defined from the following list:
•
---------
: cancellation of the programme step. No action shall be taken into account.
•
Start
: the compressor is started at the indicated time, the pressure band is used as defined in the menu
Settings.
•
Stop
: the compressor is stopped at the time indicated.
•
Settings 1
: the use of the control parameters as defined in the menu Settings for the pressure band 1 starting
from the time indicated.
•
Settings 2
: same as Settings 1 but with pressure band 2
If the compressor is part of the multi-compressor MULTILOGIC network (in option) and when it is the master
compressor, the following choices are also possible:
•
Start.sys
: is used when the controller is the master of a network of several compressors in MULTILOGIC
mode. It indicates that the entire network will be ready to start at the indicated time. The pressure band
used is the one defined in the menu Settings of the master compressor.
•
Stop sys
: is used when the controller is the master of a network of several compressors in MULTILOGIC
mode and indicates that the entire network will be stopped at the indicated time.
•
MCC P1
: is used when the controller is the master of a network of several compressors in MULTILOGIC
mode. It indicates that the entire network will be ready to start at the indicated time. The pressure band
used is the one defined in the menu MCC Settings for the band 1 of the MULTILOGIC mode.
•
MCC P 2
: is used when the controller is the master of a network of several compressors in MULTILOGIC
mode. It indicates that the entire network will be ready to start at the indicated time. The pressure band
used is the one defined in the menu MCC Settings for the band 2 of the MULTILOGIC mode
3.14 History menu
Description
This menu and its submenus allow displaying the latest errors occurred as well as a list of values of certain
parameters and inputs recorded at the time of this error.
This menu displays the data recorded during the last 5 errors.
Instruction book
2920 1804 00
55
Содержание CPF 175
Страница 1: ...CPF 175 CPVS 175 Instruction book ...
Страница 2: ......
Страница 7: ...11 Declaration of conformity 148 Instruction book 2920 1804 00 5 ...
Страница 15: ...2 2 Air and oil system Flow diagrams Flow diagram air cooled compressor Instruction book 2920 1804 00 13 ...
Страница 18: ...Flow diagram water cooled compressor with modulating control Instruction book 16 2920 1804 00 ...
Страница 33: ...Menu structure for fixed speed compressors Instruction book 2920 1804 00 31 ...
Страница 34: ...Menu structure for variable speed compressors Instruction book 32 2920 1804 00 ...
Страница 60: ...Fixed speed compressors Instruction book 58 2920 1804 00 ...
Страница 72: ...Fixed speed compressors Instruction book 70 2920 1804 00 ...
Страница 104: ...Electrical connections for IEC variable speed compressors Instruction book 102 2920 1804 00 ...
Страница 105: ...Electrical connections for CSA UL fixed speed compressors Instruction book 2920 1804 00 103 ...
Страница 151: ......