20 

Mounting 

Electrical installation 

EtherCAT 

 

 

R

 

 

4.3.7

 

EtherCAT 

Typical topologies

 

 

 

Master 

SD 

Slave Device 

 

Bus-related information 

Name 

 

EtherCAT 

 

Communication medium 

 

Ethernet 100 Mbps, full duplex 

 

Use 

 

Connection of the inverter to an 
EtherCAT network 

 

Connection system 

 

RJ45 

 

Status display 

 

2 LEDs 

 

Connection designation 

 

In: X246 
Out: X247 

 

Basic network settings

 

The rotary encoder switch allows you to set an EtherCAT identifier. 

 

 

 

x 16 

x 1

 

Setting

 

Identifier

 

0x00 

Value from parameter 

0x01 ... 0xFF 

Switch position 

Line

 

M

 

IN      OUT   IN 

OUT

 

SD1

 

SD2

 

IN

 

SDn

 

Содержание Emotron DSV15

Страница 1: ...Emotron DSV15 35 AC drive 0 25 2 2 kW Mounting and switch on instruction...

Страница 2: ...This page intentionally left blank...

Страница 3: ...ns connection 400 V 16 4 3 2 1 Fusing and terminal data 17 4 3 3 Connection to the IT system 18 4 3 4 CANopen 19 4 3 5 Modbus 20 4 3 6 PROFIBUS 21 4 3 7 EtherCAT 22 4 3 8 EtherNet IP 23 4 3 9 PROFINET...

Страница 4: ...g Please observe the safety instructions 1 2 Notations and conventions 1 2 1 Product code examples DSV15 23 1P7 20 DSV35 40 1P3 20 DSV 15 23 1P7 20 Series 1 phase 230V Rated current 1 7A IP20 DSV 35 4...

Страница 5: ...not exceed 110 VDC Observe all specifications of the corresponding documentation supplied This is the precondition forsafe and trouble free operation and for obtaining the product features specified...

Страница 6: ...motor residual movement max 180 2 90 This residual movement must be taken into consideration by the user for his her risk assessment 2 3 Application as directed The product must only be operated unde...

Страница 7: ...7 Product description 3 3 Product description...

Страница 8: ...notes Dangerous electricalvoltage Possible consequence death or severeinjuries All works on the inverter must only be carried out in the deenergised state After switching off the mains voltage wait f...

Страница 9: ...9 Mounting Mechanical installation 4 4 2 Mechanical installation Dimensions 0 25 kW 0 37 kW All dimensions in mm...

Страница 10: ...10 4 Mounting Mechanical installation Dimensions 0 55 kW 0 75 kW All dimensions in mm...

Страница 11: ...11 Mounting Mechanical installation 4 Dimensions 1 1 kW 2 2 kW All dimensions in mm...

Страница 12: ...rical installation 1 phase mains connection 230 240 V 4 3 Electrical installation 4 3 1 1 phase mains connection 230 240 V The wiring diagram is valid for Emotron DSV15 35inverters COM NC NO Fig 1 Wir...

Страница 13: ...16 25 25 25 Circuit breaker Characteristic B Max ratedcurrent A 10 10 16 16 25 25 25 Earth leakage circuit breaker 30 mA type A or B Mains connection Connection X100 Connection type Screw terminal Min...

Страница 14: ...1 4 3 2 3 phase mains connection 400 V The wiring diagram is valid for Emotron DSV 35 inverters COM NC NO Fig 3 Wiring example S1 Run Stop Fx Fuses Q1 Mains contactor Dashed line options X105 U V W Rb...

Страница 15: ...10 16 16 16 Circuit breaker Characteristic B Max ratedcurrent A 10 10 10 16 16 16 Earth leakage circuit breaker 30 mA type B Mains connection Connection X100 Connection type Screw terminal Min cable c...

Страница 16: ...ts have earth ground potential if the IT screws are not removed Consequence the monitoring functions of the IT systemrespond Before connection to an IT system be absolutely sure to remove the IT screw...

Страница 17: ...a 64 32 16 8 4 2 1 OFF OFF ON OFF ON 20 kbps OFF OFF OFF OFF OFF OFF OFF Inactive OFF OFF ON ON 50 kbps Value fromparameter ON OFF OFF ON OFF 125 kbps Node address example Active OFF OFF OFF ON 250 k...

Страница 18: ...8 4 2 1 Mode Address Bus termina tion Baud rate Parity Modbus node address R c b a 128 64 32 16 8 4 2 1 OFF n c OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Inactive Automatic detection Automatic detection...

Страница 19: ...RxD TxD N Data line A received data transmitted data 9 n c Basic networksettings Use the DIP switch to set the station address The baud rate is detectedautomatically Printed in bold CGsetting The net...

Страница 20: ...hernet 100 Mbps full duplex Use Connection of the inverter to an EtherCATnetwork Connectionsystem RJ45 Status display 2 LEDs Connection designation In X246 Out X247 Basic networksettings The rotary en...

Страница 21: ...thernet 10 Mbps 100 Mbps half duplex full duplex Use Connection of the inverter to an EtherNet IP network Connectionsystem RJ45 Status display 2 LEDs Connection designation X266 X267 Basic networksett...

Страница 22: ...I O controller SW Switch SCALANCE MRP capable D I O device R Redundant domain Bus related information Name PROFINET RT Communication medium Ethernet 100 Mbps full duplex Use Connection of the inverte...

Страница 23: ...the EN ISO 13849 2 If an external force acts upon the drive axes additional brakes are required Please observe that hanging loads are subject to the force ofgravity The user has to ensure that the inv...

Страница 24: ...onnection type Screw terminal Min cable cross section mm 0 5 Max cable cross section mm 1 5 Stripping length mm 6 Tightening torque Nm 0 2 Required tool 0 4 x 2 5 X1 Specification Unit min typ max SIA...

Страница 25: ...nstructions and safetyclearances 5 2 Before initial switch on Prevent injury to persons and damage to property Check the following before switching on the mains voltage Is the wiring complete and corr...

Страница 26: ...splays RDY and ERR on the front of the inverter a If the blue RDY LED is blinking and the red ERR LED is off the inverter is ready for operation The controller is inhibited You can now start the drive...

Страница 27: ...the function for the reversal of rotation direction again X3 DI3 LOW Speed characteristic example DI1 Drive follows frequencysetpoint AI1 V 10 0 DI4 Speed setpoint selection via X3 AI1 active t In th...

Страница 28: ...Overvoltage categoryIII EN 61800 5 1 0 2000 m a m s l Overvoltage categoryII above 2000 m a m s l Control circuit isolation Safe mains isolation by double reinforcedinsulation EN 61800 5 1 Protective...

Страница 29: ...torage 2K3 25 70 C EN 60721 3 2 Transport 3K3 10 55 C EN 60721 3 3 Operation Operation at a switching frequency of 2 or 4 kHz above 45 C reduce rated output current by 2 5 C Operation at a switching f...

Страница 30: ...2 6 7 9 6 4 kHz A 1 7 2 4 3 2 4 2 6 7 9 6 8 kHz A 1 7 2 4 3 2 4 2 6 7 9 6 16 kHz A 1 1 1 6 2 1 2 8 4 4 7 6 4 Power loss W 15 20 25 33 42 50 70 Overcurrent cycle 180s Max output current A 2 55 3 6 4 8...

Страница 31: ...3 9 5 6 4 kHz A 1 3 1 8 2 4 3 2 3 9 5 6 8 kHz A 1 3 1 8 2 4 3 2 3 9 5 6 16 kHz A 0 9 1 2 1 6 2 1 2 6 3 7 Power loss W 24 31 40 51 61 85 Overcurrent cycle 180s Max output current A 1 95 2 7 3 6 4 8 5 8...

Страница 32: ...02 2016 13500560 3 0 01 6229 01R1 CG Drives Automation Sweden AB M rsaregatan 12 Box 222 25 SE 250 24 HELSlNGBORG Sweden Tel 46 42 169900 info cgglobal com www emotron com...