19
Mounting
Electrical installation
PROFIBUS
4
R
4.3.6
PROFIBUS
Typical topologies
M
Master
X1
Repeater
Sxx
Slaves
R
Activated bus terminating resistor
Sub D socket 9-pin - X226
View
Pin
Assignment
Description
5
1
5
1
9
6
9 6
1
Shield
Additional shield connection
2
n.c.
3
RxD/TxD-P
Data line-B (received data/transmitted data +)
4
RTS
Request To Send (received data/transmitted data, no differential
signal)
5
M5V2
Reference potential (bus terminating resistor -)
6
P5V2
5 V DC / 30 mA (bus terminating re, OLM, OLP)
7
n.c.
8
RxD/TxD-N
Data line-A (received data/transmitted data -)
9
n.c.
Basic network settings
Use the DIP switch to set the station address.
The baud rate is detected automatically.
Printed in bold
= CG setting
The network must be terminated with a resistor at the physically first and last node.
Activate the bus terminating resistor at these nodes in the bus connection plug.
64 32 16 8 4 2 1
O
N
PROFIBUS Address
PROFIBUS station address
64
32
16
8
4
2
1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Value from parameter
Station address - example:
OFF
OFF
ON
OFF
ON
ON
ON
Station address = 16 + 4 + 2 + 1 = 23
Do not set station address = 126 and station address = 127. These station addresses are invalid.
R
X1
R
Line with repeater
M
R
S11
S12
S1n
S21
R
S2n
1
2
Содержание Emotron DSV15
Страница 1: ...Emotron DSV15 35 AC drive 0 25 2 2 kW Mounting and switch on instruction...
Страница 2: ...This page intentionally left blank...
Страница 7: ...7 Product description 3 3 Product description...
Страница 10: ...10 4 Mounting Mechanical installation Dimensions 0 55 kW 0 75 kW All dimensions in mm...
Страница 11: ...11 Mounting Mechanical installation 4 Dimensions 1 1 kW 2 2 kW All dimensions in mm...