Mounting
Electrical installation
Modbus
4.3.5
Modbus
Typical topologies
Terminal description
Modbus
Connection
X216
Connection type
Spring terminal
Min. cable cross-section
mm²
0.5
Max. cable cross-section
mm²
2.5
Stripping length
mm
10
Tightening torque
Nm
-
Required tool
0.4 x 2.5
Basic network settings
Use the DIP switch to set the node address and baud rate and to activate the integrated bus terminating
resistor.
R c b a 128 64 32 16 8 4 2 1
Mode
Address
Bus termina-
tion
Baud rate
Parity
Modbus node address
R
c
b
a
128
64
32
16
8
4
2
1
OFF
n.c.
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Inactive
Automatic detection
Automatic detection
Value from parameter
ON
ON
ON
Node address - example:
Active
Value from parameter Value from parameter OFF OFF OFF ON OFF ON ON ON
Node address = 16 + 4 + 2 + 1 = 23
Node address > 247: value from parameter
Printed in bold
= CG setting
The network must be terminat
ed with a 120 Ω
resistor at the physically first and last node.
Set the "R" switch to ON at these nodes.
TA
TB COM
TA
TA
TA
TB
COM
Line
A1
A2
A3
An
120
120
120
120
X216
X216
TB COM
X216
TB COM
X216
O
N
Содержание Emotron DSV15
Страница 1: ...Emotron DSV15 35 AC drive 0 25 2 2 kW Mounting and switch on instruction...
Страница 2: ...This page intentionally left blank...
Страница 7: ...7 Product description 3 3 Product description...
Страница 10: ...10 4 Mounting Mechanical installation Dimensions 0 55 kW 0 75 kW All dimensions in mm...
Страница 11: ...11 Mounting Mechanical installation 4 Dimensions 1 1 kW 2 2 kW All dimensions in mm...