![CG Emotron DSV15 Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/cg/emotron-dsv15/emotron-dsv15_manual_2585390013.webp)
13
Mounting
4
Electrical installation
1-phase mains connection 230/240 V
4.3.1.1
Fusing and terminal data
Inverter
DSV15231P7
DSV15232P4
DSV15233P2
DSV15234P2
DSV15236P0
DSV15237P0
DSV15239P6
Cable installation in
compliance with
EN 60204-1
Laying system
B2
Operation
without mains choke
Fuse
Characteristic
gG/gL or gRL
Max. rated current
A
10
10
16
16
25
25
25
Circuit breaker
Characteristic
B
Max. rated current
A
10
10
16
16
25
25
25
Operation
with mains choke
Fuse
Characteristic
gG/gL or gRL
Max. rated current
A
10
10
16
16
25
25
25
Circuit breaker
Characteristic
B
Max. rated current
A
10
10
16
16
25
25
25
Earth-leakage circuit
breaker
≥ 30 mA, type A or B
Mains connection
Connection
X100
Connection type
Screw terminal
Min. cable cross-section mm²
1
Max. cable cross-section mm²
2.5
6
Stripping length
mm
8
Tightening torque
Nm
0.5
0.7
Required tool
0.5 x 3.0
0.6 x 3.5
Motor connection
Connection
X105
Connection type
Screw terminal
Min. cable cross-section mm²
1
Max. cable cross-section mm²
2.5
Stripping length
mm
8
Tightening torque
Nm
0.5
Required tool
0.5 x 3.0
PE connection
Connection
PE
Connection type
PE screw
Min. cable cross-section mm²
1
Max. cable cross-section mm²
6
Stripping length
mm
10
Tightening torque
Nm
1.2
Required tool
0.8 x 5.5
Содержание Emotron DSV15
Страница 1: ...Emotron DSV15 35 AC drive 0 25 2 2 kW Mounting and switch on instruction...
Страница 2: ...This page intentionally left blank...
Страница 7: ...7 Product description 3 3 Product description...
Страница 10: ...10 4 Mounting Mechanical installation Dimensions 0 55 kW 0 75 kW All dimensions in mm...
Страница 11: ...11 Mounting Mechanical installation 4 Dimensions 1 1 kW 2 2 kW All dimensions in mm...