56
CET Inc.
9608
WO
Hall Zero Setting
UINT16
9609
WO
Reset Hall Zero Parameters
UINT16
Table 5-33 Clear/Reset Control Setup
Notes:
1)
The following table provides a detailed description of the different values that can be written to the
Clear Energy
and
Clear
Peak Demand of This Month (Since Last Reset)
registers to clear the different Energy and Peak Demand registers for Mains
Meter and SMs. Writing “0xAAFF” to clear all the
Energy
and
Peak Demand
of This
Month (Since Last Reset) log
for all
channels.
Key
Clear Register Values
Description
High Order
Low Order
1
0xAA
(Mains and
SMs)
0x00
Clear Mains (0x0000)
0x01
Clear SM1(0x0001)
…
…
0x11
Clear SM11 (0x0011)
0x12
Clear SM12 (0x0012)
Table 5-34 Clear Energy and Peak Demand Register Values
2)
Writing “0xFFFF” to the register clears
Energy Measurements
,
Peak Demand Log of This Month (Since Last Rest)
,
Peak
Demand Log of Last Month (Before Last Reset)
,
SOE Log
and
DR Log
that are listed in
Section 5.3
to
5.6
.
5.10 Remote Control
The DO Control registers are implemented as both “Write-Only” Modbus Coil Registers (0XXXXX) and
Modbus Holding Registers (4XXXXX), which can be controlled with the Force Single Coil command
(Function Code 0x05) or the Preset Multiple Hold Registers (Function Code 0x10). The PMC-512-D does
not support the Read Coils command (Function Code 0x01) because DO Control registers are “Write-
Only”.
The PMC-512-D adopts the ARM before EXECUTE operation for the remote control of its Digital
Outputs if this function is enabled through the
Arm Before Execute Enable
Setup register (6014), which
is disabled by default. Before executing an OPEN or CLOSE command on a Digital Output, it must be
“Armed” first. This is achieved by writing the value 0xFF00 to the appropriate register to “Arm” a
particular DO operation. The DO will be “Disarmed” automatically if an “Execute” command is not
received within 15 seconds after it has been “Armed”. If an “Execute” command is received without
first having received an “Arm” command, the meter ignores the “Execute” command and returns the
0x04 exception code.
Register
Property
Description
Format
Note
9100
WO
Arm DO Close
UINT16
Writing “0xFF00”
to the register to
perform the
described action.
9101
WO
Execute DO Close
UINT16
9102
WO
Arm DO Open
UINT16
9103
WO
Execute DO Open
UINT16
Table 5-35 DO Control
5.11 Meter Information
Register
Property
Description
Format
Note
60200
~
60219
9800
~
9819
RO
Meter model
UINT16
See Note 1)
60220
9820
RO
Firmware Version
UINT16
e.g. 10000 shows
the version is
V1.00.00
60221
9821
RO
Modbus Version
UINT16
e.g. 10 shows the
version is V1.0