52
CET Inc.
4=1000 imp/kWh
5=3200 imp/kWh
6015
RW
LED EN Pulse Mode
3
UINT16
0* to 13
6016
RW
Date Format
UINT16
0=YYYY/MM/DD*
1=MM/DD/YYYY
2=DD/MM/YYYY
6017
RW
Demo
UINT16
0=Disabled*, 1=Enabled
Table 5-24 Basic Setup
Notes:
1.
The unit of Mains CT Primary is A for Mains Current or mA for Residual Current.
2.
The Demand Log’s and Monthly Energy Log’s
Self-Read Time
support the following two options:
a)
A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
b)
A non-zero value means that the Self-Read will take place at a specific time and day based on the formula: Self-Read
Time = (Day x 100 + Hour) where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self
-
Read will take place at 12:00pm on the 15th day of each month.
3.
The
LED Energy Pulse Modes
are listed in the table below:
Value
Parameter
Value
Parameter
Value
Parameter
0
Disabled
5
SM4 kWh
10
SM9 kWh
1
Mains kWh
6
SM5 kWh
11
SM10 kWh
2
SM1 kWh
7
SM6 kWh
12
SM11 kWh
3
SM2 kWh
8
SM7 kWh
13
SM12 kWh
4
SM3 kWh
9
SM8 kWh
Table 5-25 LED Energy Pulse Modes
5.7.2 AI Setup
Register
Property
Description
Format
Range, Default*
6050
RW
AI Type
UINT16 0=4~20mA*, 1=0~20mA
6051
RW
AI Zero Scale
INT32
-999,999 to +999,999
400*
6053
RW
AI Full Scale
INT32
-999,999 to +999,999
2000*
Table 5-26 AI Setup
5.7.3 DI Setup
Register
Property
Description
Format
Range, Default*
6100
RW
DI Excitation
1
UINT16
0 = 220VDC*
1=220VAC, 2 =110VDC
3=110VAC, 4=48VDC
5=-48VDC
6101
RW
DI1 Debounce
2
UINT16
1 to 9999 ms, 40*
6102
RW
DI2 Debounce
2
UINT16
6103
RW
DI3 Debounce
2
UINT16
…
RW
…
UINT16
6112
RW
DI12 Debounce
2
UINT16
6113
RW
DI13 Debounce
2
UINT16
Table 5-27 AI Setup
Notes:
1)
For the model that supports 48VDC for DI, the DI Excitation can only be ±48V (such as PMC-512-DX43AE). For the model
that supports 240VDC for DI, the DI Excitation option are 110VAC, 110VDC, 220VAC or 220VDC (such as PMC-512-DX43BE).
2)
The DI Excitation must be set correctly for the DI Debounce to work.
5.7.4 Communication Setup Parameters
Register Property
Description
Format
Range, Default*
6200
RW
COM1 Unit ID
UINT16
1 to 254, 100*
6201
RW
COM1 Baud Rate
UINT16
0=1200, 1=2400, 2=4800, 3=9600,
4=19200, 5=38400*, 6=57600
6202
RW
COM1 Comm. Config.
UINT16
1=8O1, 2=8E1*, 3=8N1
6203
RW
COM2 Unit ID
UINT16
1 to 254, 100*
6204
RW
COM2 Baud Rate
UINT16
0=1200, 1=2400, 2=4800, 3=9600*,
4=19200, 5=38400, 6=57600
6205
RW
COM2 Comm. Config.
UINT16
1=8O1, 2=8E1*, 3=8N1
Table 5-28 Communication Setup