Current L Alarm:
Figure 4-17 Current L Alarm Logic Diagram
Current LL Alarm
Figure 4-18 Current LL Alarm Logic Diagram
4.3.7 AI Alarm
PMC-512-D provides four AI Alarm Levels (High-High, High, Low, Low-Low). The following table illustrates
the AI Alarm parameters.
Parameters
Range
Default
AI Alarm Enable
(Reg. # 6484)
0* = Disable
Bit0=HH Bit1=H Bit2=L Bit3=LL
0
AI HH Alarm Threshold
(Reg. # 6485)
-999999 to 999999
0
AI HH Alarm Time Delay
(Reg. # 6487)
0 to 9999 (s)
10 s
AI H Alarm Threshold
(Reg. # 6488)
-999999 to 999999
0
AI H Alarm Time Delay
(Reg. # 6490)
0 to 9999(s)
10 s
AI L Alarm Threshold
(Reg. # 6491)
-999999 to 999999
0
AI L Alarm Time Delay
(Reg. # 6493)
0 to 9999(s)
10 s
AI LL Alarm Threshold
(Reg. # 6494)
-999999 to 999999
0
AI LL Alarm Time Delay
(Reg. # 6496)
0 to 9999(s)
10s
AI Alarm Trigger
(Reg. # 6497)
0*=Disabled
Bit 0=DO, Bit 1=Alarm LED
Bits 2-15=Reserved
0
Table 4-11 AI Alarm Parameters