55
CET Inc.
5.7.7 Data Recorder Setup
Register Property
Description
Format
Range, Default*
6900
RW
Trigger Mode
UINT16
0=Disabled, 1=Enabled
6901
RW
Recording Mode
UINT16
0*=Stop-When-Full
1=First-In-First-Out
6902
RW
Recording Depth
UINT16
0 to 5000
6903
RW
Recording Interval
UINT32
60 to 345600s, 600*
6905
RW
Recording Offset
1
UINT16
0* to 43200s
6906
RW
Parameters Number
UINT16
0* to 60
6907
RW
Parameter1
UINT16
Please refer to Appendix B for a
complete list of the Data
Recorder Parameters.
6908
RW
Parameter2
UINT16
6909
RW
Parameter3
UINT16
…
…
UINT16
6966
RW
Parameter60
UINT16
Table 5-31 DR Parameter Setup
Note:
1.
Recording Offset < Recording Interval.
5.8 Time Registers
There are two sets of Time registers supported by the PMC-PMC-512-D – Year / Month / Day / Hour /
Minute / Second (Registers # 60000 to 60002) and UNIX Time (Register # 60004). When sending time to
the PMC-512-D over Modbus communications, care should be taken to only write one of the two Time
register sets. All registers within a Time register set must be written in a single transaction. If registers
60000 to 60004 are being written to at the same time, both Time register sets will be updated to reflect
the new time specified in the UNIX Time register set (60004) and the time specified in registers 60000-
60002 will be ignored. Writing to the Millisecond register (60003) is optional during a Time Set operation.
When broadcasting time, the function code must be set to 0x10 (Pre-set Multiple Registers). Incorrect
date or time values will be rejected by the meter. In addition, attempting to write a Time value less than
Jan 1, 2000 00:00:00 will be rejected.
Register
Property
Description
Format
Note
60000 9000
RW
High-order Byte: Year
UINT16
0-37 (Year-2000)
Low-order Byte: Month
1 to 12
60001 9001
RW
High-order Byte: Day
UINT16
1 to 31
Low-order Byte: Hour
0 to 23
60002 9002
RW
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
60003
9003
RW
Millisecond
UINT16
0 to 999
60004
~
60005
9004
~
9005
RW
UNIX Time
UINT32
0x386D4380 to 0x 7FE8177F
The corresponding time is
2000.01.01 00:00:00 to
2037.12.31 23:59:59
(GMT 0:00 Time Zone)
Table 5-32 Time Registers
5.9 Clear/Reset Control
Register
Property
Description
Format
Note
9600
WO
Clear All Latched Alarms
UINT16
Writing “0xFF00” to the
register executes the
described action
9601
WO
Clear SOE Log
UINT16
9602
WO
Clear Energy
1
UINT16
9603
WO
Clear Peak Demand of This
Month (Since Last Reset)
1
UINT16
9604
WO
Clear DR Log
UINT16
Writing “0xFF00” to the
register executes the
described action
9605
WO
Clear All
2
UINT16
9606
WO
Reset to Default
UINT16
9607
WO
Clear Monthly Energy Log
UINT16