29
CET Inc.
3.4.3 Configuration
The
Setup Configuration Mode
provides access to the following setup parameters:
Label
Description
Range
Default
Menu
1
st
2
nd
3
rd
Setup
Basic
Nom. Voltage
Nominal Voltage
48 V/240 V/336 V
240 V
Mains Current Type
Mains Current Type
Incomer/Residual
Incomer
Mains CT Primary
Mains CT Primary
1
1 to 3,000
A/mA
1
400 A/mA
1
Mains CT Secondary
Mains CT Secondary
0.1-5.0 V
4 V
Mains Breaker Rating
Mains Breaker Rating
1 to 3,000 A
250 A
Dmd Period
Demand Interval
1 to 60 min
15
No. of Windows
Number of Sliding Windows
1 to 15
1
Dmd S.R. Time
Self-Read Time for Demand
See Note 2)
0
Dmd S.R. Mode
Self-Read Mode for Demand
Auto/Manual
Auto
Mthly Energy Log S.R. Time
Self-Read Time for
Monthly Energy Log
See Note 2)
0
R.C. Arm
Enable Arm before Execute
Remote Control
Enabled/Disabled
Enabled
DO Pulse Width
Specifies the Pulse Width for
which the relay output will be
active when a remote control
command is received to activate
it. The DO is in Latched mode if
it’s set to zero.
0.0 ~600.0 s
0 s
EN Pulse CNST
LED Energy Pulse Constant
1/10/100/400/
1000/3200 imp/kWh
400
LED EN Pulse
Specifies which kWh will be
enabled as the LED Energy Pulse
0 to 14
3
0 (Disabled)
Date Format
Set Date Format
YYYY/MM/DD
MM/DD/YYYYY
DD/MM/YYYY
YYYY/MM/DD
Language
System language
EN/SC/TC
EN
SM Config.
CT Primary
SMx (x=1-12) CT Primary
1 to 3000 A
100 A
CT Secondary
SMx (x=1-12) CT Secondary
1 to 100 mA
50 mA
Breaker Rating
SMx (x=1-12) Breaker Rating
1 to 3,000 A
250 A
Comm.
COM1 Unit ID
COM1 Modbus Address
1 to 254
100
COM1 Baud Rate COM1 Data rate in bits per COM1
second
1200/2400/4800/9600
19200/38400/57600
38400
COM1 Config
COM1 Data Format
8N2/8O1/8E1/8N1
8E1
COM2 Unit ID
COM2 Modbus Address
1 to 254
100
COM2 Baud Rate
COM2 Data rate in bps
1200/2400/4800/9600/
19200/38400/57600
9600
COM2 Config
COM2 Data Format
8N2/8O1/8E1/8N1
8E1
Alarm
Global Alarm
Uni. Hys.
Universal Hysteresis
0 to 10%
2%
ON/OFF Threshold
Current ON Threshold
0 to 10%
5%
ON Time
Current ON Delay
0 to 9999(s)
10s
OFF Time
Current OFF Delay
0 to 9999(s)
30s
Voltage Alarm
H Limit
U H Alarm Limit
0~300.0V
0
H Delay
U H Alarm Delay
0~9999s
0
L Limit
U L Alarm Limit
0~300.0V
0
L Delay
U L Alarm Delay
0~9999s
0
Trigger
U Alarm Trigger
None/DO/Alarm
LED/DO & Alarm LED
None
Mains Current Alarm
4
HH Threshold
Current HH Alarm Threshold
0 to 100 (%)
5
80%
HH Delay
Current HH Alarm Delay
0 to 9999 (s)
10s
H Threshold
Current H Alarm Threshold
0 to 100 (%)
5
60%