54
CET Inc.
0*
6496
RW
AI LL Alarm Time Delay
UINT16
0 to 9999 (s), 10*
6497
RW
AI Alarm
Trigger
UINT16
0* to 0x0003
Table 5-29 Alarm Setup Parameters
Notes:
1)
The calculation method for the
Universal Hysteresis
is listed below:
Universal Hysteresis=
∣
Alarm Threshold-Alarm Return Threshold
∣
Alarm Threshold
×%
2)
If the
Threshold/Limit
is set to 0, the corresponding channel alarm is disabled.
3)
The
Incomer Current Alarm
is invalid when the
Mains Current Type
is
Residual
.
4)
The
Residual Current Alarm
is invalid when the
Mains Current Type
is
Incomer
.
5)
Bits 0 to 11 represent the
SM Current Alarm Enable
for SM1 to 12 respectively, with the bit value “0” meaning Disabled and
“1” meaning Enabled. For example, 0x003F means SM1 to 6 are enabled for
Current Alarm
and SM7 to 12 are disabled.
6)
0x03 stands for 2 bits (BIN). Bit 0 and 1 represents RO trigger enable and Alarm LED enable respectively. For every bit,
0=Alarm Disabled and 1=Alarm Enabled. For example, 0x03 means that both RO trigger and Alarm LED are enabled for
AI
Alarm
.
5.7.6 SM Setup Parameters
Register Property
Description
Format
Range, Default*
6600
WO
SM CT Primary (Bulk)
UINT16
1 to 3000A
6601
WO
SM CT Secondary (Bulk)
UINT16
1 to 100mA
6602
WO
SM Breaker Rating (Bulk)
UINT16
1 to 3000A
6603
RW
SM1 CT Primary
UINT16
1 to 3000 (A), 100*
6604
RW
SM1 CT Secondary
UINT16
1 to 100 (mA), 50*
6605
RW
SM1 Breaker Rating
UINT16
0 to 3000A, 63*
6606
RW
SM2 CT Primary
UINT16
1 to 3000 (A), 100*
6607
RW
SM2 CT Secondary
UINT16
1 to 100 (mA), 50*
6608
RW
SM2 Breaker Rating
UINT16
0 to 3000A, 63*
6609
RW
SM3 CT Primary
UINT16
1 to 3000 (A), 100*
6610
RW
SM3 CT Secondary
UINT16
1 to 100 (mA), 50*
6611
RW
SM3 Breaker Rating
UINT16
0 to 3000A, 63*
6612
RW
SM4 CT Primary
UINT16
1 to 3000 (A), 100*
6613
RW
SM4 CT Secondary
UINT16
1 to 100 (mA), 50*
6614
RW
SM4 Breaker Rating
UINT16
0 to 3000A, 63*
6615
RW
SM5 CT Primary
UINT16
1 to 3000 (A), 100*
6616
RW
SM5 CT Secondary
UINT16
1 to 100 (mA), 50*
6617
RW
SM5 Breaker Rating
UINT16
0 to 3000A, 63*
6618
RW
SM6 CT Primary
UINT16
1 to 3000 (A), 100*
6619
RW
SM6 CT Secondary
UINT16
1 to 100 (mA), 50*
6620
RW
SM6 Breaker Rating
UINT16
0 to 3000A, 63*
6621
RW
SM7 CT Primary
UINT16
1 to 3000 (A), 100*
6622
RW
SM7 CT Secondary
UINT16
1 to 100 (mA), 50*
6623
RW
SM7 Breaker Rating
UINT16
0 to 3000A, 63*
6624
RW
SM8 CT Primary
UINT16
1 to 3000 (A), 100*
6625
RW
SM8 CT Secondary
UINT16
1 to 100 (mA), 50*
6626
RW
SM8 Breaker Rating
UINT16
0 to 3000A, 63*
6627
RW
SM9 CT Primary
UINT16
1 to 3000 (A), 100*
6628
RW
SM9 CT Secondary
UINT16
1 to 100 (mA), 50*
6629
RW
SM9 Breaker Rating
UINT16
0 to 3000A, 63*
6630
RW
SM10 CT Primary
UINT16
1 to 3000 (A), 100*
6631
RW
SM10 CT Secondary
UINT16
1 to 100 (mA), 50*
6632
RW
SM10 Breaker Rating
UINT16
0 to 3000A, 63*
6633
RW
SM11 CT Primary
UINT16
1 to 3000 (A), 100*
6634
RW
SM11 CT Secondary
UINT16
1 to 100 (mA), 50*
6635
RW
SM11 Breaker Rating
UINT16
0 to 3000A, 63*
6636
RW
SM12 CT Primary
UINT16
1 to 3000 (A), 100*
6637
RW
SM12 CT Secondary
UINT16
1 to 100 (mA), 50*
6638
RW
SM12 Breaker Rating
UINT16
0 to 3000A, 63*
Table 5-30 SM Setup Parameters