50
CET Inc.
5.5.2 Peak Demand Log of This Month (Since Last Reset)
Register
Property
Description
Format
Scale
Unit
4000
RO
Mains Current Demand*
FP32
x1
A
4002
RO
Timestamp
UINT32
s
4004
RO
SM1 Current Demand
FP32
x1
A
4006
RO
Timestamp
UINT32
s
4008
RO
SM2 Current Demand
FP32
x1
A
4010
RO
Timestamp
UINT32
s
…
…
4048
RO
SM12 Current Demand
FP32
x1
A
4050
RO
Timestamp
UINT32
s
4052
RO
Mains kW Demand*
FP32
x1
A
4054
RO
Timestamp
UINT32
s
4056
RO
SM1 kW Demand
FP32
x1
W
4058
RO
Timestamp
UINT32
s
4060
RO
SM2 kW Demand
FP32
x1
W
4062
RO
Timestamp
UINT32
s
…
…
4100
RO
SM12 kW Demand
FP32
x1
W
4102
RO
Timestamp
UINT32
s
*When
Mains Current Type
is
Residual
, this register is invalid
Table 5-19 Peak Demand Log of This Month (Since Last Reset)
5.5.3 Peak Demand Log of Last Month (Before Last Reset)
Register
Property
Description
Format
Scale
Unit
4104
RO
Mains Current Demand*
FP32
x1
A
4106
RO
Timestamp
UINT32
s
4108
RO
SM1 Current Demand
FP32
x1
A
4110
RO
Timestamp
UINT32
s
4112
RO
SM2 Current Demand
FP32
x1
A
4114
RO
Timestamp
UINT32
s
…
…
4152
RO
SM12 Current Demand
FP32
x1
A
4154
RO
Timestamp
UINT32
s
4156
RO
Mains kW Demand*
FP32
x1
A
4158
RO
Timestamp
UINT32
s
4160
RO
SM1 kW Demand
FP32
x1
W
4162
RO
Timestamp
UINT32
s
4164
RO
SM2 kW Demand
FP32
x1
W
4166
RO
Timestamp
UINT32
s
…
…
4204
RO
SM12 kW Demand
FP32
x1
W
4206
RO
Timestamp
UINT32
s
*When
Mains Current Type
is
Residual
, this register is invalid
Table 5-20 Peak Demand Log of Last Month (Before Last Reset)
5.6 Log Register
5.6.1 SOE Log
Register
Property
Description
Format
10000-10008
RO
Event 1
See Appendix A
SOE Log Data
Structure
10009-10017
RO
Event 2
10018-10026
RO
Event 3
10027-10035
RO
Event 4
….
….
14599~14607
RO
Event 512
Table 5-21 SOE Log