31
CET Inc.
Notes:
1)
The
unit of
Mains CT Primary
is variable, which is A or mA, and depends on whether the
Mains Current Type
is
Incomer
or
Residual
.
2)
The
Dmd
S.R. Time
and
Mthly Energy Log S.R Time
support the following two options:
a.
A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
b.
A non-zero value means that the Self-Read will take place at a specific time and day based on the formula: Self-Read
Time = (Day x 100 + Hour) where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the
Self-
Read will take place at 12:00pm on the 15th day of each month.
3)
The
LED Energy Pulse Modes
are listed in the table below:
Value
Parameter
Value
Parameter
Value
Parameter
0
Disabled
5
SM4 kWh
10
SM9 kWh
1
Mains kWh
6
SM5 kWh
11
SM10 kWh
2
SM1 kWh
7
SM6 kWh
12
SM11 kWh
3
SM2 kWh
8
SM7 kWh
13
SM12 kWh
4
SM3 kWh
9
SM8 kWh
Table 3-10 LED Energy Pulse Modes
4)
Since the
Mains Current Type
can be configured as
Incomer
or
Residual
, the
Current Alarm
settings should be configured
accordingly. When
Incomer
is selected as the
Mains Current Type
, the
Mains Current Alarm
settings would be used for
alarming, and vice versa.
5)
The available options for DIx Excitation would depend on the PMC-512-D Model. The 48VDC and -48VDC options are only
available for the hardware that is only equipped with 48VDC DI while the 220VDC, 220VDC, 110VDC and 110VAC options
are available for the 240VDC (max.336VDC) DI.
3.4.4 Maintenance
Parameters
Descriptions
Range
Default
Clock Setup
Time and Date
YYYY/MM/DD
hh:mm:ss
-
Password Setup
Set New Password
-
-
BLTO
Backlight Time Out
1
0 to 60 min.
5
Contrast
LCD Contrast
0 to 9
5
Auto-Scroll
Auto Scroll Setup
2
See Note 2)
Clear Energy
Clear all Energy registers
Yes/No
No
Clear Max Demands
Clear Peak Demand Log of This Month
(Since Last Reset)
Yes/No
No
Clear All Demands
Clear all Demand Logs
Yes/No
No
Clear SOE
Clear SOE Logs
Yes/No
No
Clear DR Log
Clear DR Logs
Yes/No
No
Clear All Data
Clear All of the above
Yes/No
No
Factory Reset
Reset factory default settings
Yes/No
No
Table 3-11 Maintenance Parameters
Notes:
1)
If
BLTO
is set to 0, the Backlight Time Out is disabled, which means that the Backlight will always be on.
2)
Auto-Scroll
Setup allows users to select which
SM
and whether
Analog Input
would be displayed in
Auto-Scroll Mode
. For
Example, if the PMC-512-D is used for monitoring 9 branch circuits with SM1 to SM9, the remaining three SMs can be
disabled in the
Auto-Scroll
Mode
to prevent unnecessary information from being displayed. The
Parameter Categories
and
their measurements are listed in the table below, and all of them are
Enabled
in
Auto-Scroll Mode
by default. The
Parameter
Category
Mains Circuit
is always shown and cannot be disabled in
Auto-Scroll
mode.
Parameter Categories
Measurements
Mains Circuit
U
I*/Ir~
%Loading
1
P
1
kWh
1
SMx (x=1-12)
Ix
%Loadingx
Px
kWhx
AI
AI Scaled
AI Raw
*I stands for the Mains Current when working with Mains Circuit Hall Effect CT.
~Ir stands for the Residual Current when working with DC Residual Hall Effect CT.
Note:
1)
When the
Mains Current Type
is
Residual Current
, %Loading, P, and kWh are not available.
Table 3-12 Auto-Scroll Display Pages