21
28-05-02
Fig. 5:4a Balanced Flue Terminal Positions
Table to above Flue Terminal Positions - MINIMUM dimensions
REF
DESCRIPTION
DISTANCE IN mm
A
Directly below an Opening, Air Brick or Window
600
B
Below a Gutter, Sanitary Pipework or Eaves
600*
C
From an Internal Corner
900
D
Above Ground
700
E
From a surface facing a Terminal
2000
F
From a Terminal facing a Terminal
2000
G
Vertically between Two Terminals on the same wall
1500
H
Horizontally between Two Terminals on the same wall
1200
J
From an External Corner
600
K
Horizontally from an Opening, Air Brick, Window or Door
600
Horizontally from Outdoor Terminal
600
Above an Outdoor Terminal
3000
* Where the Terminal is within 1m of any plastic material, such material should be shielded from the
effects of the combustion products of the flues.
The Flue Terminal positions given are as recommended by the Manufacturer. The final position of the flue
should be checked with the local Building Inspectorate.