CF1043
Remote Off Disable
AC InPower
This parameter change the attribution of the
remote ON/OFF input.
If parameter is 1, then, when system is in remote
OFF position, output is not stopped and AC input
is stopped instead.
0
0
0
-
CF1044
Reinjection allowed
If this parameter is 1, the converter is allowed to
inject power in the grid with its AC input.
0
1
1
-
CF1045
External clock
Records the “External Clock” mode configuration
0 - no protection in: phase drift is allowed.
1 - protection in: no phase drift allowed, stops
the system after 1 minute.
2 - System stops immediately.
0
0
2
-
CF1046
Walk in mode
The Walk-in mode allows the converter to come
back progressively on the AC priority source after
an outage. Friendly use on Genset.
0
0
60
-
CF1047
Triangle mode
Defines the protection type for working on Delta
load.
0 - Default setting, and no delta load protection
1 - The mode is active. If one output phase
stops, the other phases will also stop.
0
0
1
-
CF1048
Airco Mode
When this mode is activated, the overload
capabilities are moved from default value
to 330% overload in current and power for
maximum 900 ms.
0
0
0
-
CF1049
Start without
supervision
When this mode is activated, the converter is
able to start without Inview.
0
1
1
-
CF1050
P DC Max
This feature allow to limit or reduce the INRUSH
DC current when the system work on battery. To
limit the current this configuration line should
limit the inrush DC current.
To allow for the high capability this converter is
build with extra capacitor running on 400VDC to
provide the requested energy.
0
0
1
-
CF1051
AC 1 stop power
Stops the power of the corresponding AC group.
The AC input of the converters of this AC group
will then be used for synchronisation only, no
power will be taken.
0
0
1
-
CF1052
AC 2 stop power
0
0
1
-
CF1053
AC 3 stop power
0
0
1
-
CF1054
AC 4 stop power
0
0
1
-
CF1055
St module Number
NA
0
0
0
-
CF1056
St module
Redundancy
NA
0
0
0
-
CF1057
Tus
Mode TUS activation.
0
0
1
-
CF1058
Tus modules
number
Number of TUS modules in the system (typically
2) -> number of tus seen by local supervision.
0
0
24
-
65
– Sierra 10 - 48/120 VAC – User Manual – v1.1
Appendix