11. Trouble Shooting and Defective Situations Fixing
11.1 Trouble Shooting
Converter module does not power up:
Check AC input present and in range (AC breakers)
Check DC input present and in range (DC breakers)
Check that the converter is properly inserted
Remove converter to verify that slot is not damaged, check connectors
Check that module(s) is (are) in OFF state
Check
for
loose
terminations
Converter system does not start:
Check that Inview is present and properly connected
Check
remote
ON/OFF
terminal
Check the configuration and setting
Check
threshold
level
Converter only run on AC or DC:
Check AC input present and in range (AC breakers)
Check DC input present and in range (DC breakers)
Check the configuration and setting
Check
threshold
level(s)
No output power:
Check output breaker
All OK but I have alarm:
Check the type of event and log file in the controller
No alarm:
Check relay delay time of alarms in the controller
Check
configuration
file
47
– Sierra 10 - 48/120 VAC – User Manual – v1.1
Trouble Shooting and Defective Situations Fixing