6.4.9.1 Remote ON/OFF
The shelf is by default equipped with a connection between pin 3 and 2. If remote ON/OFF is not used the strap shall
remain in all connected shelves. Should the remote ON/OFF be used, all straps must be removed and in one (1) shelf
replaced with a changeover contact or emergency button.
•
The remote ON/OFF switch the output AC OFF.
•
Input AC and input DC is not affected by the remote ON/OFF.
•
The remote ON/OFF can be connected to any shelf.
•
The remote ON/OFF requires changeover contacts, one input opens as the other close.
If both transitions are not picked up the status is not changed.
Relay characteristics (Remote ON/OFF)
•
Signal voltage
+5 VDC (galvanic insulated)
•
Max wire size
1 mm
2
Functional table for remote ON/OFF function
#
Pin 1-3
Pin 2-3
Status
Indication
1
Open
Open
Normal operation
All (Green)
2
Closed
Open
OFF
AC output (OFF)
AC Input (Green)
DC Input (Green)
3
Open
Closed
Normal operation
All (Green)
4
Closed
Closed
Normal operation
All (Green)
Warning! If remote ON/OFF is not used, pin 2 and 3 MUST be bridged together.
6.4.9.2 Internal bus (BUS A / BUS B)
•
In a la carte system, Internal bus is pre installed and connected in series
from the first shelf to last shelf.
•
Internal bus is comprised of 6 and 8 pole CAN bus cables.
•
If more than one shelf is ordered separately and installed in others
cabinet, 6 and 8 pin connector of each shelf should be connected in
series with all shelf using CAN bus cables.
•
The internal bus connectors are sensitive and special caution should be
taken during installation to keep them out of harms way.
BUS A Cable
BUS B Cable
6 Pin
8 Pin
29
– Sierra 10 - 48/120 VAC – User Manual – v1.1
System Installation