6.4.6 AC Input and Output
WARNING !!!
Recommendation of IEC 60364 4. 43
431.3 Disconnection and reconnection of the neutral conductor in multi-phase systems
Where disconnection of the neutral conductor is required, disconnection and reconnection shall be such that the
neutral conductor shall not be disconnected before the line conductors and shall be reconnected at the same
time as or before the line conductors.
WARNING !!!
Input Neutral is required to operate the
Inverter, UPS
In TN-S System no 4 pole input switch or
circuit breaker shall be used. If you have to
use 4 pole protective device, be aware that
the neutral against the ground is floating.
The inverter, UPS will operate without
problem but you may infringe the local
regulation.
L1
L2
L3
N
PE
Local
TFO
Circuit
Breaker
Converter
UPS
Model
Configuration
Maximum
Capacity
Current @
120 Vac
MCB
per Shelf
Cable
Minimum*
S71A33CDD04SNF00G00H
Single-Phase
2 Wires
(L-N)
4 kVA / 3.2 kW
37 A
50 A
4 AWG
S71A33CDD05SNF00G00H
5 kVA / 4 kW
47 A
60 A
4 AWG
S71A63CDD04SNF00G00H
Split-Phase
3 Wires
(L1-L2-N)
4 kVA / 3.2 kW
19 A
25 A
10 AWG
S71A63CDD08SNF00G00H
8 kVA / 6.4 kW
37 A
50 A
4 AWG
S71A63CDD10SNF00G00H
10 kVA / 8 kW
47 A
60 A
4 AWG
S71A53CDD12SNF00G00H
Three-Phase
4 Wires
(L1-L2-L3-N)
12 kVA / 9.6 kW
37 A
50 A
4 AWG
S71A53CDD15SNF00G00H
15 kVA / 12 kW
47 A
60 A
4 AWG
* One conductor / pole - 90°C
Note:
•
The Icc value measured as 60 Arms per shelf with five modules.
•
The current values are calculated based on correction factor of 75% with respect to ambient temperature of
40°C.
26
– Sierra 10 - 48/120 VAC – User Manual – v1.1
System Installation