3.3.2 Surge and transients
The mains (AC) supply of the modular inverter system shall be equipped with Lightning surge suppression and
Transient voltage surge suppression suitable for the application. Follow manufacturer’s recommendation for
installation. Selecting a device with an alarm relay for function failure is advised.
All sites are considered to have a working lightning surge suppression device in service and installed close enough to
ensure effective protection in accordance with best industry practice.
•
Indoor sites Min Class II.
•
Outdoor sites Min Class I + Class II or combined Class I+II. The modular inverter system/rack can reach
hazardous leakage currents. Earthing must be carried out prior to energizing the system. Earthing shall be made
according to local regulations.
3.3.3 Other
•
Insulation test (Hi-Pot) must not be performed without instructions from the manufacturer. Irreparable damage
may occur.
3.4 Maintenance
•
The modular inverter system/rack can reach hazardous leakage currents. Earthing must be carried out prior to
energizing the system. Earthing shall be made according to local regulations.
•
Prior to any work conducted on a system/unit make sure that AC input voltage and DC input voltage are
disconnected.
•
CAUTION
– Risk of electric shock. Inverter modules and shelves contain capacitors for filtering and energy
storage. Prior to accessing the system/modules after power down, wait at least 5 minutes to allow capacitors to
discharge.
•
CAUTION
–
During system operation, the system and module surfaces will be hot. Do not touch, and
contact may cause severe burns. So, please turn off the power and allow it to cool before accessing.
•
Some components and terminals carry high voltage during operation. Contact may result in fatal injury.
3.5 Replacement and Dismantling
•
ESD Strap must be worn when handling PCB’s and open units.
•
CE+T cannot be held responsible for disposal of the Inverter system and therefore the customer must segregate
and dispose of the materials which are potentially harmful to the environment, in accordance with the local
regulations in force in the country of installation.
•
If the equipment is dismantled, to dispose of its component products, you must comply with the local regulations
in force in the country of destination and in any case avoid causing any kind of pollution.
To download the latest documentation and software, please visit our website at www.cet-power.
com
10
– Sierra 10 - 48/120 VAC – User Manual – v1.1
Warranty and Safety Conditions
Содержание Sierra 10 - 48/230
Страница 67: ......