ID
Name
Description
Min
Default
Max
Unit
AC Inputs
CF301
Override Power
Limitation Timeout
The timeout after the defined voltage, which the
system returns in normal condition.
0
20
60
s
CF1068
Default Power
Limitation
global peak-shaving (-1 if no peak-shaving)
0
-1
800
W
CF1006
Low Start
AC IN Voltage where a higher value leads the AC
IN to start
80
92.5
144
V
CF1007
Low Transfer
AC IN Voltage where a lower value leads to the
transfer of the load from the AC IN to DC IN
80
87.5
144
V
CF1008
Low Stop
AC IN Voltage where a lower value leads the AC
IN converter to stops.
It is possible to step down to 150 Vac. In this
case, the AC/DC converter will run at a lower
power.
The converter DC/DC supply the rest (Only if DC
is available, if not, there is a de-rating)
80
87.5
144
V
CF1009
High Start
AC IN Voltage where a lower value leads the AC
IN converter re-start
80
133
144
V
CF1010
High Transfer
AC IN Voltage where a higher value leads to the
transfer the load of the charge from the AC IN
converter to the DC IN converter
80
138
144
V
CF1011
High Stop
AC IN Voltage where a higher value leads to stop
the AC IN converter.
80
138
144
V
CF1012
Low Start
Frequency where a higher value leads the outlet
of the converters trying to synchronize with AC
IN.
47
57.3
63
Hz
CF1013
Low Stop
Frequency where a lower value leads the outlet
of converters stop to synchronize with AC IN.
47
57
63
Hz
CF1014
High Start
Frequency where a lower value leads the
converters outlet to synchronize with AC IN.
47
62.7
63
Hz
CF1015
High Stop
Frequency where a higher value leads the
converters outlet to stop to synchronize with AC
IN.
47
63
63
Hz
DC
CF501
Override Voltage
SetPoint Timeout
The timeout after the defined voltage, which the
system returns in normal condition.
0
20
60
s
CF503
Override Power
SetPoint Timeout
The timeout after the defined power, which the
system returns in normal condition.
0
20
60
s
CF1000
Low Start
Low DC Voltage where a higher value leads the
DC/AC converter to re-start.
39
44
61
V
CF1001
Low Transfer
Low DC Voltage where a lower value leads to
transfer the load from DC IN to AC IN. Under this
voltage peak-shaving is relaxed and battery
discharge test is stopped.
39
390
610
V
63