14.2
Fuses and Fuse Code for UL
Bussmann Div Cooper (UK) Ltd
(200 kARMS Symmetrical A.I.C.)
Ferraz Shawmut SA
(200 kARMS Symmetrical A.I.C.)
SIZE
Fuse
CODE
Current
(ARMS)
I²T
(A²sec)
Vac
Fuse
CODE
Current
(ARMS)
I²T
(A²sec) Vac
Qty
15A FWC
16A10F 16
150 600
660 Grb
10-16
16 145
660
1
25A FWC
32A10F 32
600 600
660 Grb
10-32
32 740
660
1
35A FWP
40A14F 40
750 700
CP URC
14x51/40
40 700
660
1
45A FWP
50A14F 50
1800 700
CP URC
14x51/50
50 1500
660
1
60A FWP
80A22F 80
6600 700
CP URD
22x58/80
80 3800
660
1
90A -
- - -
CP URQ
27x60/125
125 6970
660
1
110A -
- - - CP URQ
27x60/160
160 15000
660
1
Caution:
The Fuses must have I²t 20% less than thyristor's I²t.
Caution:
High speed fuses are used only for the thyristor protection and can not be used to
protect the installation.
Caution:
The warranty of thyristor is null if no proper fuses are used. See tab.
Warning:
The user installation must be protected by electromagnetic circuit breaker or by
fuse isolator.
C
US
LISTED
UL
®