CD Automation srl
CD3200-1PH from 15A to 110A
User’s Manual
43
P125L (H7D)
Byte Lo = Feed-Back Type
R/W
Function:
This parameter set the Feed-Back Type
Value:
00 Hex = V2
20 Hex = V
40 Hex = I
80 Hex = VxI
Default:
20 (if not specified in the Order Code)
P125H (H7D)
Byte Hi = Soft start time
R/W
Function:
The Unit starts in phase angle mode with a ramp starting from zero up to full
voltage in a presetted and Adjustable time.
The time is setted by this parameter
Min/Max:
0 ÷ 255 (0 ÷FF Hex)
Value:
Each step is 50msec
Default:
20
(S+PA)
P126L (H7E)
Byte Lo = HB Delay time
R/W
Function:
This parameter set a delay to have HB alarm active
Min/Max:
1 ÷ 255 (0 ÷ FF Hex)
Value:
Each step is 50msec
Default:
30 (if not specified in the Order Code)
Note:
If Soft start option is enabled HB Delay time must be greater than Soft start
time: P126L x 50msec > P125H x 50msec
P126H (H7E)
Byte Hi = HB sensibility
R/W
Function:
This parameter is the maximum reduction of Load Current to establish the HB
Alarm
Min/Max:
0 ÷ 100 (0 ÷64 Hex)
Value:
Each step is 1% from Nominal Current
Default:
14
Hex
Note:
When you change this parameter, HB Calibration procedure is necessary.
P127 (H7F)
Power Set
R/W
Function:
This parameter show the Power set saved by the Calibration Procedure
Min/Max:
0 ÷ 65535 (0 ÷ FFFF Hex)
Value:
from 0 = 0% output power,
to 65535 = 100% output power.
P128L (H80)
Byte Lo = Integral
R/W
Function:
This parameter is the integral time of the feed-back loop
Min/Max:
0 ÷ 255 (0 ÷FF Hex)
Default:
50
Hex
Note:
If you increase integral time you increase the output stability, but you increase
also the time to reach the set.
P128H (H80)
Byte Hi = Proportional
R/W
Function:
This parameter is the gain of the feed-back loop
Min/Max:
0 ÷ 255 (0 ÷FF Hex)
Default:
VxI or V2 = 5 Hex
V or I =12 Hex
Note:
This parameter increase the loop speed but decrease the loop stability.