CD Automation srl
CD3200-1PH from 15A to 110A
User’s Manual
29
11.2
Supply the Electronic Board
The CD3200 thyristor unit, to work, requires a voltage supply for the electronic boards. The Max
consumption is 10VA.
The voltage supply for the electronic boards is configured in line with customer requirements that are
defined in the Order Code. The Order Code is written on the identification label.
Warning:
Before connecting or disconnecting the unit check that power and control cables
are isolated from voltage sources.
Terminal
Description
16
Voltage Supply for Electronic Boards (Auxiliary Voltage)
17 Earth
18
Voltage Supply for Electronic Boards (Auxiliary Voltage)
To change auxiliary supply voltage sold the correct link-jumper on main PCB:
Warning:
this procedure can be done just by specialized personnel.
Link-Jumper J9+J11
Main PCB
Link-Jumper J9+J11
Transformer Type
Link-Jumper J9+J11
Link-Jumper J10
TR-605 120V
90:130V
-
TR-605 230V
170:265V
300:530V
TR-605 300V
230:345V
510:690V
•
The type of mounted transformer depends of the chosen Auxiliary Voltage in the order code.
(see par. 5.2)
•
If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the
load), use an external transformer with primary equal to load voltage and secondary equal to the
Auxiliary Voltage.
J9
J10
J11
J9
J10
J11
J9
J10
J11