CD Automation srl
CD3200-1PH from 15A to 110A
User’s Manual
36
11.8
Address configuration
The thyristor unit is assigned a unique device address by the user in the range 1 (default) to
255. This address is used to recognise the messages queries to her assigned.
The thyristor unit does not respond at the messages queries that don't have the same assigned address.
The thyristor unit will also accept global messages (Broadcast) sends at the address 0. No responses are
returned for globally addressed queries.
To configure communication address remove cover and set the dip-switch as below specified:
Dip Switch
Convert the Address Number in Binary for Example:
150 Dec = 10010110 Bin
The dip switch number corresponds to the bit number:
Dip Switch Number
Address Number
8 7 6 5 4 3 2 1
150 Dec -> 10010110 Bin
1
(On)
0
(Off)
0
(Off)
1
(On)
0
(Off)
1
(On)
1
(On)
0
(Off)
For convert the Number in Binary you can use this method:
Dip Switch Number have this value:
Dip Switch Number
8 7 6 5 4 3 2 1
Value
128
64
32
16 8 4 2 1
The Address Number Ex. 150 = 128(Dip 8) + 16(Dip 5) + 4(Dip 3) + 2(Dip2)