CD Automation srl
CD3200-1PH from 15A to 110A
User’s Manual
42
P006 (H06)
Power adjust
R/W
Function:
Its’ a scaling factor of the Input command signal
Min/Max:
0 ÷ 255 (0 ÷FF Hex)
Value:
from 0 = 0% of Output,
To 255 = 100% of Output.
Note:
This parameter limit the Output Power
100
Power Adjust = 100%
Power Adjust = 80%
Power Adjust = 40%
80
60
40
20
0
40
20
60
100
80
Input %
OUT %
P007 (H07)
Current Limit
R
Function:
This parameter show the Current Limit value (see par. 10.3)
When the P004 Bit4 =1 This parameter could be written and become the
Current Limit from RS485
Min/Max:
0 ÷ 255 (0 ÷ FF Hex)
Value:
Value depends on when turns have current transformer and from his size’s
Example:
With one passage on the current transformer (CT) 25/0.05A, the max value
corresponds to the max value of the CT:
Read value=255 (FF Hex) -> Load Current= 25A
P121 (H79)
CD Unit ID
R
Function:
This parameter Identify the CD type Family
Value:
CD32 Hex = CD3200 Family
P122 (H7A)
CD Ver
R
Function:
This parameter is for internal use
P123 (H7B)
Password
R/W
Function:
This parameter give the access to configuration
Min/Max:
0 ÷ FFFF Hex
Value:
9357 Hex = Writing parameters activated
any value = Writing parameters disabled
Note:
When the unit comes out and then re-lighted, for change the parameters you
must re-insert the password.
P124 (H7C)
Actual power
R
Function:
This parameter show the actual value of the power demand
Min/Max:
0 ÷ 65535 (0 ÷ FFFF Hex)
Value:
from 0 = 0% output power,
to 65535 = 100% output power.