CD Automation srl
CD3200-1PH from 15A to 110A
User’s Manual
46
14.3
Fuses and Fuse Code for CE
SIZE
Fuse
and Fuse holder
CODE
Fuse CODE
Current
(ARMS)
I²T (max)
(A² sec.)
15A FFH1038/16A FU1038/16A
16
150
25A FFH1038/32A FU1038/32A
32
600
35A FFH1451/40A FU1451/40A
40
1650
45A FFH1451/50A FU1451/50A
50
2000
60A FFH2258/80A FU2258/80A
80
6550
90A FFH2258/125A FU2258/125A 125
14000
110A FFH2760/160A FU2760/160A
160
15000
Caution:
The Fuses must have I²t 20% less than thyristor's I²t.
Caution:
High speed fuses are used only for the thyristor protection and can not be used to
protect the installation.
Caution:
The warranty of thyristor is null if no proper fuses are used. See tab.
Warning:
The user installation must be protected by electromagnetic circuit breaker or by
fuse isolator.