CD Automation srl
CD3200-1PH from 15A to 110A
User’s Manual
17
7.2
Wiring details
Use copper cables and wires rated for use at 75°C only.
7.2.1
Power cable torque (suggested)
Current
Connector
Type
Torque
Lb-in (N-m)
Wire
Range
AWG / kcmil
Wire
Terminal
15A,25A
35A,45A
M5 Screw
26.6 (3.0)
8
UL Listed (ZMVV)
Wire Pin
60A,90A
110A
M6 Screw
70.8 (8.0)
1
UL Listed (ZMVV)
Fork/Spade Terminal
Copper Tube Crimp. Lug
7.2.2
Power cable dimensions (suggested)
Supply
Load
Current Cable Screw Cable Screw
mm² AWG M mm² AWG M
15A
(S0C)
4 12 M5 4 12 M5
25A
(S0C)
6 10 M5 6 10 M5
35A
(S3C)
10 8 M5 10 8 M5
45A
(S3C)
10 8 M5 10 8 M5
60A
(S7C)
16 6 M6 16 6 M6
90A
(S7C)
35 3 M6 35 3 M6
110A
(S8C)
35 3 M6 35 3 M6
7.2.3
Cable dimensions (suggested) of Earth and of the Command Terminals
Earth
Command
Terminals
Current Cable Screw Cable
mm² AWG M mm² AWG
15A (S0C)
4
12
M5
0,50
18
25A (S0C)
6
10
M5
0,50
18
35A (S3C)
6
10
M5
0,50
18
45A (S3C)
6
10
M5
0,50
18
60A (S7C)
6
10
M5
0,50
18
90A (S7C)
6
10
M5
0,50
18
110A (S8C)
6
10
M5
0,50
18