231
* 41 for Supply Fan Motor VFD, 42 for Exhaust Fan Motor VFD.
* Depends on unit.
APPENDIX D
—
VFD INFORMATION (CONT)
Table B — VFD Parameters Configured by Carrier Assistant
PARAMETER GROUP
PARAMETER TITLE
PARAMETER INDEX
HVAC DEFAULT
CARRIER DEFAULT
Options
COMM PROT SEL
9802
NOT SEL (0)
LEN (6)
EFB Protocol
EFB PROTOCOL ID
5301
0000 hex
0601 hex
EFB STATION ID
5302
0
41/42*
EFB BAUD RATE
5303
9.6 kb/s
38.4 kb/s
EFB PARITY
5304
8 NONE 1
8 NONE 1
EFB CTRL PROFILE
5305
ABB DRV LIM
DCU PROFILE
Table C — VFD Parameters with CCN Points Configured with
Comfort
Link Controls
PARAMETER
GROUP
PARAMETER
TITLE
PARAMETER
INDEX
HVAC DEFAULT
CARRIER
DEFAULT
CCN POINT
SUPPLY FAN VFD
CCN POINT
EXHAUST FAN
VFD
Start-Up Data
MOTOR NOM VOLT
9905
230V,460V,575V
*
VFD1NVLT
VFD2NVLT
MOTOR NOM
CURR
9906
1.0*In
*
VFD1NAMP
VFD2NAMP
MOTOR NOM
FREQ
9907
60 Hz
60 Hz
VFD1NFRQ
VFD2NFRQ
MOTOR NOM
SPEED
9908
1750 rpm
1750 rpm
VFD1NRPM
VFD2NRPM
MOTOR NOM
POWER
9909
1.0*Pn
*
VFD1NPWR
VFD2NPWR
Start/Stop/Dir
DIRECTION
1003
FORWARD
REQUEST
VFD1MDIR
VFD2MDIR
Accel/Decel
ACCELER TIME 1
2202
30.0s
30.0s
VFD1ACCL
VFD2ACCL
DECELER TIME 1
2203
30.0s
30.0s
VFD1DECL
VFD2DECL
Motor Control
SWITCHING FREQ
2606
4 kHz
8 kHz
VFD1SWFQ
VFD2SWFQ
Table D — VFD Parameters Configured with
Comfort
Link Controls
PARAMETER GROUP
PARAMETER TITLE
PARAMETER INDEX
HVAC DEFAULT
CARRIER DEFAULT
Start/Stop/Dir
EXT1 COMMANDS
1001
DI1
COMM (10)
Reference Select
REF1 SELECT
1103
AI1
COMM (8)
Constant Speeds
CONST SPEED SEL
1201
DI3
NOT SEL (0)
CONST SPEED 7
1208
60 Hz
0 Hz
System Controls
RUN ENABLE
1601
NOT SEL
NOT SEL (0)
FAULT RESET SEL
1604
KEYPAD
COMM (8)
START ENABLE 1
1608
DI4
DI4 (4)
Start/Stop
START FUNCTION
2101
SCALAR FLYSTART
AUTO (1)
STOP FUNCTION
2102
COAST
RAMP (2)
Fault Functions
COMM FAULT FUNC
3018
NOT SEL
CONST SP 7 (2)
COMM FAULT TIME
3019
10.0 s
10.0 s
Automatic Reset
AR OVERCURRENT
3104
Disable (0)
Disable (0)
AR OVERVOLTAGE
3105
Enable (1)
Disable (0)
AR UNDERVOLTAGE
3106
Enable (1)
Disable (0)
AR AI<MIN
3107
Enable (1)
Disable (0)
AR EXTERNAL FAULT
3108
Enable (1)
Disable (0)
Содержание WeatherExpert 48N2
Страница 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Страница 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Страница 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Страница 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Страница 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Страница 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Страница 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Страница 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Страница 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Страница 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Страница 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Страница 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Страница 168: ...168 Fig 47 Sensor and Ignition Position Fig 48 Combustion Blower Details SENSOR DETAILS IGNITION DETAILS ...
Страница 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...