49
Table 29 —
Setpoints
Cool Mode Determination
If the machine control type (
Configuration
UNIT
C.TYP
) =
1 (VAV-RAT) or 2 (VAV-SPT) and the control is occupied (
Oper
-
ating Modes
MODE
OCC
=ON
), then the unit will not follow
the occupied cooling set point (
OCSP
). Instead, the control will
follow 2 offsets in the determination of an occupied VAV cooling
mode (
Setpoints
V.C.ON
and
Setpoints
V.C.OF
), applying
them to the low-heat off trip point and comparing the resulting
temperature to the controlling return temperature (
R.TMP
).
The
Setpoints
V.C.ON
(VAV cool mode on offset) and
Set
-
points
V.C.OF
(VAV cool mode off offset) offsets are used in
conjunction with the low heat mode off trip point to determine
when to bring cooling on and off and in enforcing a true “vent”
mode between heating and cooling. See Fig. 4. The occupied cool
-
ing set point is not used in the determination of the cool mode. The
occupied cooling set point is used for supply air reset only.
Fig. 4 —
VAV Occupied Period Trip Logic
The advantage of this offset technique is that the control can
safely enforce a vent mode without worrying about crossing set
points. Even more importantly, under CCN linkage, the occu
-
pied heating set point may drift up and down and as such this
technique of using offsets ensures a guaranteed separation in
degrees F between the calling out of a heating or cooling mode
at all times.
VAV Occupied Cool Mode Evaluation Configuration
There are VAV occupied cooling offsets under
Setpoints
.
NOTE: There is a submenu at the local display (
Run Status
TRIP
) that allows the user to see the exact trip points for
both the heating and cooling modes without having to calculate
them. Refer to the Cool Mode Diagnostic Help section on
page 51 for more information.
To enter into a VAV Occupied Cool mode, the controlling tem
-
perature must rise above
[
OHSP
minus
L.H.ON
plus
L.H.OF
plus
V.C.ON
].
To exit out of a VAV Occupied Cool Mode, the controlling
temperature must fall below
[
OHSP
minus
L.H.ON
plus
L.H.OF
plus
V.C.ON
minus
V.C.OF
].
NOTE: With vent mode, it is possible to exit out of a cooling
mode during the occupied period if the return-air temperature
drops low enough. When supply-air temperature reset is not
configured, this capability will work to prevent over-cooling
the space during the occupied period.
Supply Air Set Point Control and the Staging of Compressors
Once the control has determined that a cooling mode is in ef
-
fect, the cooling control point (
Run Status
VIEW
CL.C.P
)
is calculated and is based upon the supply air set point (
Set
-
points
SASP
) plus any supply air reset being applied (
In
-
puts
RSET
SA.S.R
).
Refer to the SumZ Cooling Algorithm section on page 51 for a
discussion of how the N Series
Comfort
Link controls manage
the staging of compressors to maintain supply-air temperature.
EX.SL
EXV Init Pos Slope
–100 to 100
EXV_SLP
–0.4
EX.IN
EXV Init Pos Intercept
–200 to 200
EXV_INT
66
EX.SM
EXV Smoothing Algorithm
0 to 1
EXV_SMAL
0
EX.EP
SH Error Exponent
1 to 1.5
ERR_POW
1.3
DP.OC
DP OVERRIDE CONFIGS
DP.RS
DP Rate of Change Set
2 to 15
°psig
DP_RC_ST
10
DP.RC
DP Rate of Change Clr
0 to 5
°psig
DP_RC_CL
1
DP.L1
DP Override Limit 1
400 to 450
psig
DP_OD_L1
400
DP.L2
DP Override Limit 2
480 to 550
psig
DP_OD_L2
500
DP.TO
DP Override Timeout
6 to 150
sec
DP_OD_TO
90
DP.OR
DP Override Percent
0 to 15
%
DP_OD_PT
10
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
OHSP
Occupied Heat Setpoint
40-99
dF
OHSP
68
OCSP
Occupied Cool Setpoint
40-99
dF
OCSP
75
UHSP
Unoccupied Heat Setpoint
40-99
dF
UHSP
55
UCSP
Unoccupied Cool Setpoint
40-110
dF
UCSP
90
GAP
Heat-Cool Setpoint Gap
2-10
^F
HCSP_GAP
5
V.C.ON
VAV Occ. Cool On Delta
0-25
^F
VAVOCON
3.5
V.C.OF
VAV Occ. Cool Off Delta
1-25
^F
VAVOCOFF
2
SASP
Supply Air Setpoint
45-75
dF
SASP
55
SA.HI
Supply Air Setpoint Hi
45-75
dF
SASP_HI
55
SA.LO
Supply Air Setpoint Lo
45-75
dF
SASP_LO
60
SA.HT
Heating Supply Air Setpt
90-145
dF
SASPHEAT
85
T.PRG
Tempering Purge SASP
–20-80
dF
TEMPPURG
50
T.CL
Tempering in Cool SASP
5-75
dF
TEMPCOOL
5
T.V.OC
Tempering Vent Occ SASP
–20-80
dF
TEMPVOCC
65
T.V.UN
Tempering Vent Unocc. SASP
–20-80
dF
TEMPVUNC
50
Table 28 —
Cooling Configuration (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
L.H.OF
DMDLHOFF
L.H.ON
DMDLHON
V.C. ON
VAVOCON
V.C. OF
VAVOCOFF
OH
S
P
a48-8414
ITEM
EXPANSION RANGE UNITS
CCN
POINT
DEFAULT
V.C.ON
VAV Occ.
Cool On Delta
0 to 25 deltaF VAVOCON
3.5
V.C.OF
VAV Occ.
Cool Off Delta
1 to 25 deltaF VAVOCOFF
2
Содержание WeatherExpert 48N2
Страница 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Страница 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Страница 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Страница 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Страница 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Страница 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Страница 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Страница 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Страница 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Страница 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Страница 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Страница 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Страница 168: ...168 Fig 47 Sensor and Ignition Position Fig 48 Combustion Blower Details SENSOR DETAILS IGNITION DETAILS ...
Страница 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...