201
ECON (cont)
ECONOMIZER CONFIGURATION (cont)
EC.DY
T24 Econ Auto-Test Day
0=Never,
1=Monday,
2=Tuesday,
3=Wednesday,
4=Thursday,
5=Friday,
6=Saturday,
7=Sunday
T24_ECDY
6=Saturday
EC.TM
T24 Econ Auto-Test Time
0 - 23
T24_ECTM
2
BP
BUILDING PRESS. CONFIGS
BP.CF
Building Press. Config
0 to 2
BLDG_CFG
0*
BP.S
Building Pressure Sensor
Disable/Enable
BPSENS
Disable*
BP.R
Bldg. Press. (+/-) Range
0.1 to 0.25
"H2O
BP_RANGE
0.25
BP.SP
Building Pressure Setp.
-0.25 to 0.25
"H2O
BPSP
0.05
BP.SO
BP Setpoint Offset
0 to 0.5
"H2O
BPSO
0.05
B.V.A
VFD/ACTUATOR CONFIG
BP.FS
VFD Fire Speed
0 to 100
%
BLDGPFSO
100
BP.MN
VFD Minimum Speed
0 to 100
%
BLDGPMIN
10
BP.MX
VFD Maximum Speed
0 to 100
%
BLDGPMAX
100
FAN.T
FAN TRACKING CONFIG
FT.CF
Fan Track Learn Enable
No/Yes
DCFM_CFG
No
FT.TM
Fan Track Learn Rate
5 to 60
min
DCFMRATE
15
FT.ST
Fan Track Initial DCFM
-20000 to 20000
CFM
DCFMSTRT
2000
FT.MX
Fan Track Max Clamp
0 to 20000
CFM
DCFM_MAX
4000
FT.AD
Fan Track Max Correction
0 to 20000
CFM
DCFM_ADJ
1000
FT.OF
Fan Track Internl EEPROM
-20000 to 20000
CFM
DCFM_OFF
0
FT.RM
Fan Track Internal RAM
-20000 to 20000
CFM
DCFM_RAM
0
FT.RS
Fan Track Reset Internal
No/Yes
DCFMRSET
No
FAN.C
SUPPLY, RET/EXH FAN CFG
SCF.C
Supply Air CFM Config
1 to 2
SCFM_CFG
2
REF.C
Ret/Exh Air CFM Config
1 to 2
RECFMCFG
2
SCF.S
Supply Air CFM Sensor
Disable/Enable
SCFMSENS
Disable*
RCF.S
Return Air CFM Sensor
Disable/Enable
RCFMSENS
Disable*
ECF.S
Exhaust Air CFM Sensor
Disable/Enable
ECFMSENS
Disable*
B.PID
BLDG.PRESS.PID CONFIGS
BP.TM
Bldg.Pres.PID Run Rate
1 to 60
Seconds
BPIDRATE
10
BP.P
Bldg.Press. Prop. Gain
0 to 5
BLDGP_PG
0.5
BP.I
Bldg.Press. Integ. Gain
0 to 2
BLDGP_IG
0.5
BP.D
Bldg.Press. Deriv. Gain
0 to 5
BLDGP_DG
0.3
D.LV.T
COOL/HEAT SETPT. OFFSETS
L.H.ON
Dmd Level Lo Heat ON
0 to 2
^F
DMDLHON
1.5
H.H.ON
Dmd Level(+) Hi Heat ON
0.5 to 20
^F
DMDHHON
0.5
L.H.OF
Dmd Level(-) Lo Heat OFF
0.5 to 2
^F
DMDLHOFF
1
L.C.ON
Dmd Level Lo Cool ON
0 to 2
^F
DMDLCON
1.5
H.C.ON
Dmd Level(+) Hi Cool ON
0.5 to 20
^F
DMDHCON
0.5
L.C.OF
Dmd Level(-) Lo Cool OFF
0.5 to 2
^F
DMDLCOFF
1
C.T.LV
Cool Trend Demand Level
0.1 to 5
^F
CTRENDLV
0.1
H.T.LV
Heat Trend Demand Level
0.1 to 5
^F
HTRENDLV
0.1
C.T.TM
Cool Trend Time
30 to 600
Seconds
CTRENDTM
120
H.T.TM
Heat Trend Time
30 to 600
Seconds
HTRENDTM
120
DMD.L
DEMAND LIMIT CONFIG.
DM.L.S
Demand Limit Select
0 to 3
DMD_CTRL
0
D.L.20
Demand Limit at 20 ma
0 to 100
%
DMT20MA
100
SH.NM
Loadshed Group Number
0 to 99
SHED_NUM
0
SH.DL
Loadshed Demand Delta
0 to 60
%
SHED_DEL
0
SH.TM
Maximum Loadshed Time
0 to 120
Minutes
SHED_TIM
6
D.L.S1
Demand Limit Sw.1 Setpt.
0 to 100
%
DLSWSP1
80
D.L.S2
Demand Limit Sw.2 Setpt.
0 to 100
%
DLSWSP2
50
IAQ
INDOOR AIR QUALITY CFG.
DCV.C
DCV ECONOMIZER SETPOINTS
EC.MN
Economizer Min.Position
0 to 100
%
ECONOMIN
5
IAQ.M
IAQ Demand Vent Min.Pos.
0 to 100
%
IAQMINP
0
O.C.MX
Economizer Min.Flow
0 to 20000
CFM
OACFMMAX
2000
O.C.MN
IAQ Demand Vent Min.Flow
0 to 20000
CFM
OACFMMIN
0
O.C.DB
Econ.Min.Flow Deadband
200 to 1000
CFM
OACFM_DB
400
AQ.CF
AIR QUALITY CONFIGS
IQ.A.C
IAQ Analog Sensor Config
0 to 4
IAQANCFG
0
IQ.A.F
IAQ 4-20 ma Fan Config
0 to 2
IAQANFAN
0
APPENDIX A
—
LOCAL DISPLAY TABLES (CONT)
MODE — CONFIGURATION
(cont)
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
Содержание WeatherExpert 48N2
Страница 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Страница 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Страница 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Страница 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Страница 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Страница 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Страница 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Страница 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Страница 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Страница 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Страница 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Страница 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Страница 168: ...168 Fig 47 Sensor and Ignition Position Fig 48 Combustion Blower Details SENSOR DETAILS IGNITION DETAILS ...
Страница 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...