Appendix A: VAV Zone II Points/Properties
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
82
Service Configuration
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Configuration
>
Service Configuration
Point Name/Description
Default/Range
Terminal Type
– The type of zone terminal that the controller is installed on. Not
available for VAVB1.
D:
R:
Single Duct
Single Duct
Parallel
Series Fan
Terminal Size
– Shows the value entered as the
Cooling Max Airflow
in the
Flow Control
object.
D:
R:
2100 cfm
(991.2 liters/second)
0 to 99999 cfm
(liters/second)
Terminal Fan Airflow
– Enter the terminal fan airflow in cfm (liters/second). Used in
performance calculations only. Available only on fan-enabled terminal box.
D:
R:
1000 cfm
(472 liters/second)
0 to 99999 cfm
(liters/second)
Disable Series Fan
– When set to
Enable
, the controller disables the fan on a series-
type terminal when the airflow setpoint equals 0. (We do not recommend configuring
the minimum occupied airflow setpoint to 0, as this does not meet minimum ventilation
requirements.)
D:
R:
N/A
N/A
Enable
External Actuator Enable
– Enable if the controller's analog output is used for an
external high-torque or slave actuator. Enabling this setting disables the output for
Modulating Hot Water or Combination reheat functions.
D:
R:
Disable
Disable/Enable
Heat Type
– The type of supplemental reheat that the zone controller will control. The
heat may be used with system heat, depending on the space temperature demand.
Options:
None
– no heat
Modulating
– ducted or baseboard modulating hot water
Two Position
– two position hot water
Staged EH
– ducted or baseboard electric heat
Combination
– combination baseboard modulating hot water and ducted staged
electric heat
CV Modulating
– constant volume modulating reheat used for single duct terminal
application with modulating hot water reheat (typically used in hospital applications)
SCR Electric
– modulating control for SCR-type electric heater
D:
R:
None
None
Modulating
Two Position
Staged EH
Combination
CV Modulating
SCR Electric
Ducted Heat
– Determines whether the zone is using ducted heat or baseboard. If
Heat
Type
is
Combination
, set this field to
Yes
for ducted heat.
D:
R:
Yes
No/Yes
VAV Reheat
– If set to
Enable
and
Heat Type
is
Modulating
, a need for heat first
modulates the supply air temperature up to the configured
Maximum Heating SAT
(95ºF [35°C] default). A further heating demand will increase the airflow from the
minimum rate up to the configured
Auxiliary Heat Min Airflow
. Applicable to single duct
terminals only.
D:
R:
Enable
Disable/Enable