Appendix B: VAV terminal modes
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
98
Air Source
Mode
Temperature
Control
Requirement
Terminal
Type
Aux
Heat
Terminal
Mode
Damper Control
(Damper Setpoint
used)
Heat
Control
Fan
Control
Off
None
All
N/A
Off
Hold Damper @ 70%
(None)
Disable
Disable
Cooling
All
N/A
Off
Hold Damper @ 70%
(None)
Disable
Disable
Heating
Single Duct
N/A
Off
Hold Damper @ 70%
(None)
Disable
N/A
Series or
Parallel Fan
No
Off
Hold Damper @ 70%
(None)
Disable
Disable
Series Fan
Yes
Heating
Hold Damper @ 70%
(None)
Enable
Enable
Parallel Fan
Yes
Heating
Close Damper (None)
Enable
Enable
Vent
None
Single Duct
N/A
Heating
Minimum cfm (Vent)
Disable
N/A
Series Fan
N/A
Vent
Minimum cfm (Vent)
Disable
Enable
Parallel Fan
N/A
Vent
Minimum cfm (Vent)
Disable
Disable
Cooling
Single Duct
N/A
Cooling
Modulate Min/Max cfm
(Cool)
Disable
N/A
Series Fan
N/A
Cooling
Modulate Min/Max cfm
(Cool)
Disable
Enable
Parallel Fan
N/A
Cooling
Modulate Min/Max cfm
(Cool)
Disable
Disable
Heating
Single Duct,
Parallel Fan
No
Cooling
Minimum cfm (Cool)
Disable
Disable
Series Fan
No
Heating
Minimum cfm (Cool)
Disable
Enable
Single Duct
Yes
Reheat
Minimum cfm
Enable
N/A
Series or
Parallel Fan
Yes
Heating
Minimum cfm (Cool)
Enable
Enable
Cool,
Freecool
None
Single Duct
N/A
Vent
Minimum cfm (Cool)
Disable
N/A
Series Fan
N/A
Vent
Minimum cfm (Cool)
Disable
Enable
Parallel Fan
N/A
Vent
Minimum cfm (Cool)
Disable
Disable
Cooling
Single Duct
N/A
Cooling
Modulate Min/Max cfm
(Cool)
Disable
Disable
Series Fan
N/A
Cooling
Modulate Min/Max cfm
(Cool)
Disable
Enable
Parallel Fan
N/A
Cooling
Modulate Min/Max cfm
(Cool)
Disable
Disable
Heating
Single Duct,
Parallel Fan
No
Cooling
Minimum cfm (Cool)
Disable
Disable
Series Fan
No
Heating
Minimum cfm (Cool)
Disable
Enable
Single Duct
Yes
Reheat
Minimum cfm
Enable
N/A
Series or
Parallel Fan
Yes
Heating
Minimum cfm (Cool)
Enable
Enable