Appendix A: VAV Zone II Points/Properties
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
85
Point Name/Description
Default/Range
Flow Measurement Units
– The flow measurement output. Do not change the
default of
cfm
(liters/second).
D: cfm (liters/second)
Damper Motor Travel Time
– The actuator's travel time from full closed to full
open. Leave this field at 205 seconds.
D: 205 seconds
Direction Clockwise
– If
Damper Actuator
is set to
Built-in actuator
, set this field
to the damper's position when it rotates clockwise.
D:
R:
Open
Close/Open
Target Damper Position
- The current damper position. To override normal
control for troubleshooting purposes, select
Lock value to
and then enter a value.
The damper moves to that position until
Lock value to
checkbox is cleared.
R: 0 to 100%
Auxheat
- The current configured
Reheat Min Damper Position
. To override
normal control for reheat troubleshooting purposes, select
Lock value to
and then
enter a value. The damper moves to that position until
Lock value to
checkbox is
cleared.
R: 0 to 100%
Fan
– The current value of the fan output relay. To override normal control for
troubleshooting purposes, select
Lock value to
and then enter
On
or
Off
. The relay
stays in that state until the
Lock value to
checkbox is cleared.
R: Off/On
Cooling Max Airflow
– The maximum airflow the terminal will supply when trying
to meet a zone cooling demand when the air source mode is Cooling, Vent, or
Free Cooling.
D:
R:
2100 cfm
(991.2 liters/second)0 to
99999 cfm
(liters/second)
Heating Max Airflow
– The maximum airflow the terminal will supply when trying
to meet a zone heating demand when the air source mode is Heating or Warm-up
and
VAV heating
has been enabled.
D:
R:
2100 cfm
(991.2 liters/second)0 to
99999 cfm
(liters/second)
Occupied Min Airflow
– The minimum airflow setpoint the terminal controls to
when the air source is operating and the terminal mode is occupied.
D:
R:
315 cfm
(148.9 liters/second)
0 to 99999 cfm
(liters/second)
Unoccupied Min Airflow
– The minimum airflow setpoint the terminal controls to
when the air source is operating and the terminal mode is unoccupied.
D:
R:
315 cfm
(148.9 liters/second)
0 to 99999 cfm
(liters/second)
Auxiliary Heat Min Airflow
– ONLY used for Single Duct units with ducted reheat.
Set to the minimum airflow specified by the manufacturer to allow the reheat to
provide optimum performance. This value is compared to the appropriate
Min
Airflow
value above and the greater of the two values determines the damper
position. For all other terminal types, set to 0.
D:
R:
1680 cfm
(793 liters/second)
0 to 99999 cfm
(liters/second)
Manufacturer's specified airflow at 1" water column
– The damper
manufacturer’s rated cfm airflow at 1" water column of velocity pressure. Refer to
the manufacturer’s documentation to obtain the correct value.
D:
R:
2100 cfm
(991.2 liters/second)
0 to 99999 cfm
(liters/second)
Use supply air for heating when Heat Mode is ON
— This must be checked for all
applications. To only use the minimum airflow in heating, set
Service
Configuration
>
VAV Heating
to
Disable
.
D:
R:
Checked
Checked/Unchecked