Appendix A: VAV Zone II Points/Properties
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
86
Point Name/Description
Default/Range
Test and Balance
– Use the following command buttons when commissioning a zone, balancing the system,
replacing the zone controller, or troubleshooting. If
Automatic Control
is not selected within 4 hours, the controller
will resume normal control.
Zero Flow
– Closes the damper, takes a number of flow samples, then sets the zero calibration.
Damper Full Open
– Opens damper fully and enables the
Damper Full Open
calibration fields.
Cool Max Airflow
– Forces the damper to its maximum cooling position. Calibration fields apply only if the primary
use of this damper is cooling.
Occupied Min Airflow
– Forces the damper to its maximum cooling position. Calibration fields apply only if the
primary use of this damper is cooling.
Automatic Control
– Returns the damper to its normal control routines.
This must be activated when you finish
using any of the other Test and Balance commands.
Close
Damper
– Forces the damper to its full closed position.
Heat Max Airflow
– Forces the damper to its maximum heating position. Calibration fields apply only if the primary
use of the damper is heating.
Sensor Binder / Zone Temp / Zone Humidity / ZS Zone CO2
Ctrl+click
on the name of these properties to access the microblock popup
Properties
page >
Details
tab. See below for instructions on configuring your ZS or wireless sensors.
See the microblock Help for more detailed explanations.
Sensor Binder
- Use the
Associated Sensors
table to configure the Rnet to use additional
ZS or wireless sensors.
Network Type
- Set to
Rnet
Address
- Enter the DIP switch settings that are on the additional ZS sensors (up to 5
total) or RnetID assigned to each wireless sensor in SensorBuilder
Lock Display
- Check to make the sensor display-only
D:
(Index)
- (1)
Network Type
- Rnet
Address
- 1