Appendix A: VAV Zone II Points/Properties
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
74
Occupied Setpoints
The occupied setpoints described below are the setpoints under normal operating conditions. The Demand Level 1–3
setpoints apply if demand limiting is used.
Demand limiting is a cost-saving strategy to reduce energy consumption. The strategy expands the occupied heating and
cooling setpoints when the system reaches one of 3 levels of consumption. With the expanded setpoints, the equipment
works less, thereby saving energy. By default, Demand Level 1 expands the occupied heating and cooling setpoints by
1 °F ( .5°C), Demand Level 2 by 2 °F (1.1 °C), and Demand Level 3 by 4 °F (2.2 °C). If the occupied heating or
cooling setpoints change, the (effective) demand level setpoints automatically change by the same amount. See
Sequence of Operation
(page 48) for more information.
Default
Range:
-40 to 245°F (-40 to 118.3°C)
Demand Level
Point Name/Description
Occupied
1
2
3
Occupied Heating
– Green
The heating setpoint the controller maintains while in occupied
mode.
D:
R:
70°F
(21.1°C)
40 to 90°F
(4.4 to
32.2°C)
69°F
(20.5°C)
68°F
(20°C)
66°F
(18.9°C)
Occupied Cooling
– Green
The cooling setpoint the controller maintains while in occupied
mode.
D:
R:
76°F
(24.4°C)
55 to 99°F
(12.7 to
37.2°C)
77°F
(25°C)
78°F
(25.5°C)
80°F
(26.6°C)
Occupied Heating 1
– Light Blue
The space temperature must be less than the
Occupied Heating
1
setpoint for the VVT Master to consider the zone a heating
caller in a linked system. In a single-zone application, the heating
requirement begins as soon as the space temperature falls
below the
Occupied Heating
setpoint. We recommend that the
Occupied Heating 1
value be set no less than 0.5 °F (.27 °C)
below the
Occupied Heating
setpoint.
69°F
(20.5°C)
68°F
(20°C)
67°F
(19.4°C)
65°F
(18.3°C)
Occupied Heating 2
– Dark Blue
The space temperature must be less than the
Occupied Heating
2
setpoint to generate a low space temperature alarm. We
recommend that this value be set no less than 0.5 °F (.27 °C)
below the
Occupied Heating 1
setpoint.
67°F (19.4°C)
66°F
(18.9°C)
65°F
(18.3°C)
63°F
(17.2°C)
Occupied Cooling 1
– Yellow
The space temperature must be greater than the
Occupied
Cooling 1
setpoint for the VVT Master to consider the zone a
cooling caller in a linked system. In a single-zone application, the
cooling requirement begins as soon as the space temperature
exceeds the
Occupied Cooling
setpoint. We recommend that the
Occupied Cooling 1
value be set no less than 0.5 °F (.27 °C)
above the
Occupied Cooling
setpoint.
77°F
(25°C)
78°F
(25.5°C)
79°F
(26.1°C)
81°F
(27.2°C)
Occupied Cooling 2
– Orange
The space temperature must be greater than the
Occupied
Cooling 2
setpoint to generate a high space temperature alarm.
We recommend that this value be set no less than 0.5 °F
(.27 °C) above the
Occupied Cooling 1
setpoint.
79°F
(26.1°C)
80°F
(26.6°C)
81°F
(27.2°C)
83°F
(28.3°C)