Appendix A: VAV Zone II Points/Properties
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
81
Point Name/Description
Default/Range
IAQ/Ventilation Alarm
Occupied High CO2 Alarm Limit
– The value that the CO
2
sensor must exceed to
generate an
Indoor Air Quality Alarm
in the occupied mode if
DCV Control
is set to
Enable
. There is a fixed hysteresis of 100ppm for return to normal.
D:
R:
1100ppm
0 to 9999 ppm
Alarm Delay (min/ppm)
– The fractional portion of a minute used to determine the
amount of delay before an indoor air quality alarm is generated when the controller
transitions to the occupied mode. The delay time equals this value multiplied by the
difference between the sensor CO
2
value and the setpoint plus 15 minutes.
D:
R:
0.25 minutes
0.10 to 1.00 minutes
Alarms Displayed on ZS or SPT Sensor
Space Temperature Alarm
– If set to display, shows the alarm indicator on the
communicating zone sensors, if the
Space Temperature
alarm is active.
D:
R:
Ignore
Ignore/Display
Supply Air Temp Alarm
– If set to display, shows the alarm indicator on the
communicating zone sensors, if the
Supply Air Temp
alarm is active.
D:
R:
Ignore
Ignore/Display
Dirty Filter Alarm
– If set to display, shows the alarm indicator on the communicating
zone sensors, if a
Filter
alarm is active.
D:
R:
Display
Ignore/Display
Space High Humidity Alarm
– If set to display, shows the alarm indicator on the
communicating zone sensors with display, if the
Space Relative Humidity
alarm is
active.
D:
R:
Ignore
Ignore/Display
Space High CO2 Alarm
– If set to display, shows the alarm indicator on the
communicating zone sensors with display if the
Indoor Air Quality Alarm
is in alarm.
D:
R:
Ignore
Ignore/Display
Maintenance Displayed on ZS Sensor
Linkage Fault
– If set to display, shows the maintenance indicator on the ZS Pro sensor
if the Airside Linkage is in a Fault condition.
D:
R:
Ignore
Ignore/Display
Net OAT Fault
– If set to display, shows the maintenance indicator on the ZS Pro sensor
if the Network Outside Air is not valid.
D:
R:
Ignore
Ignore/Display
SPT Sensor Fault
– If set to display, shows the maintenance indicator on the ZS Pro
sensor if the space temperature sensor is not valid.
D:
R:
Ignore
Ignore/Display
Содержание VAV Zone II