Appendix C: ZS Sensor display for VAV Zone II
VAV Zone II Controllers
CARRIER CORPORATION ©2019
Installation and Start-up Guide
All rights reserved
100
Property
ZS Screen
Rnet Tag
Rnet Text
1
Description
Active Alarms
Diagnostic
1550
-nonE
StP-AL
SPco2-AL
SP_rH-AL
Sat-AL
No Active Alarms
Zone Temp Alarm
Zone CO2 Alarm
Zone Humidity Alarm
Supply Air Temp Alarm
Active Maintenance
Diagnostic
1551
-nonE-
SnSr-FLt
Fltr-dtY
Llnc-FLt
No Active Maintenance
Sensor Fault
Dirty Filter
Linkage Fault
Active Air Source Linkage
Mode
Diagnostic
1552
OFF
hEAt-uP
hEAt
cooL
FrEEcool
PrESSrZE
EuAcuATE
vEnt
no-Llnc
Off
Warm-up
Heat
Cool
Freecool
Pressurize
Evacuate
Vent
Linkage Not Active
Supply Air Temp
Info
304
Air Source Supply Air
Temp, if available
Air Flow Percentage of
Nominal
Info
308
% of design air flow
Outdoor Air Temperature
Info
F°
Outside Air Temp
1
Rnet text is the scrolling text that appears on the ZS Pro Sensor's display.
NOTES
To view properties on the
Diagnostic
Screen, hold the button for 3 seconds. Tap the button to cycle through
information to help troubleshoot your system.
The Rnet tag is displayed on the ZS sensor display.
To view properties on the Info Screen, press the button. Tap the button to cycle through information.
Appendix C: ZS Sensor display for VAV Zone II
Содержание VAV Zone II