Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Chilled Water System Optimizer v2
CARRIER CORPORATION ©2019
Installation and Start-up Guide
72
All rights reserved
Point Name/Description
Range
Automatic "Pause & Hold" Override of the Optimizer Reset & Pause at its Current
Reset Setpoint
1.
Pause Reset if CHWRT is >__ degrees
D:
R:
46°F
45 to 50°F
with hysteresis of __
D:
R:
1°F
1 to 3°F
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
D:
R:
4:00 (mm:ss)
2:00 to 10:00 (mm:ss)
2.
OR Pause Reset if CHWRT-CHWST is <__degrees
D:
R:
6°F
2 to 7°F
with hysteresis of __
D:
R:
1°F
1 to 3°F
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
D:
R:
4:00 (mm:ss)
2:00 to 10:00 (mm:ss)
3.
OR Pause Reset if Building Relative Humidity is > __%
D:
R:
60%
50 to 100%
with hysteresis of __
D:
R:
2%
2 to 10%
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
D:
R:
20:00 (mm:ss)
10:00 to 60:00 (mm:ss)
Use the __ building relative humidity from networked sensor values to determine
if it is too high.
Current Building Relative Humidity is __.__% — Displays value.
D:
R:
Average
Average/Maximum
4.
OR Pause Reset if Load is > __% capacity
D:
R:
90%
70 to 100%
with hysteresis of __
%
D:
R:
5%
2 to 10%
__(Pause is default, Algorithm will Cool Down otherwise)
D:
R:
Pause
Pause/Cool Down
5.
OR Pause Reset, for a remote condition, if the “Remote Pause” BBV receives a
binary ON signal
D:
R:
60%
50 to 100%
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
D:
R:
20:00 (mm:ss)
10:00 to 60:00 (mm:ss)
Automatic Pause & Hold of Chilled Water Reset - Status