Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Chilled Water System Optimizer v2
CARRIER CORPORATION ©2019
Installation and Start-up Guide
59
All rights reserved
General Conditions & Status
Navigation:
i-Vu®
Properties
>
Control Program
>
General Conditions & Status
Point Name/Description
Range
Optimizer Enable
— Displays ENABLED or DISABLED status.
Outdoor Air Temperature
— Allows this controller to use an outdoor temperature value
from another controller over the network. The remote controller must be equipped with a
network-accessible sensor value.
Allows lockout if
Lock at value:
is checked. Allows communication if
Enabled?:
is
checked.
D:
D:
Unlocked (checked)
Enabled (checked)
Outdoor Air Humidity —
Allows using another controller's relative humidity value over the
network. The remote controller must be equipped with a network-accessible value.
Allows lockout if
Lock at value:
is checked. Allows communication if
Enabled?:
is
checked.
D:
D:
Unlocked (checked)
Enabled (checked)
Outdoor Air Wet Bulb Temperature
—
Displays the calculated value based on the OA
temperature and OA humidity values.
Total Chilled & Condenser Water System kW
—
Displays the current value of all the
monitored energy loads.
Total Building Cooling Load Tons
— Displays the current value of all the monitored chilled
water system thermal load.
Total Chilled & Condenser Water System kW/ton —
Displays the current value of all the
monitored energy loads as a function of the operating thermal load of the plant.
R:
0 to 5 kW/Ton