Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Chilled Water System Optimizer v2
CARRIER CORPORATION ©2019
Installation and Start-up Guide
63
All rights reserved
Section 2 - Chiller System Power, Efficiency, and Thermal Load Input
Status
Navigation:
i-Vu®
Properties
>
Control Program
>
General Conditions & Status
>
Section 2 - Chiller
System Power, Efficiency and Thermal Load Input Status
1
Verify network connections are operating. See
Device Address Binding
(page 45).
2
Input the nominal chiller capacities (tons) required to determine part load conditions.
3
Select whether the power input is actual kW or amperage.
4
Select load input type using temperatures and flow or cooling load input.
5
Enter voltage and power factors from the equipment's specifications.
Point Name/Description
Range
The following are statuses displayed from the linked network points. See
Device
Address Binding
(page 45).
Total Chiller kW
— Displays value.
Total Chilled Water Pump kW
— Displays value.
If "Amp" network inputs are used for CHWP kW determination, then:
The voltage is ___ volts
— Enter value.
The Power Factor is __.
— Enter value.
Total Condenser Water Pump kW
— Displays value.
If "Amp" network inputs are used for CWP kW determination, then:
The voltage is ___ volts
— Enter value.
The Power Factor is __.
— Enter value.
Total Cooling Tower Fan kW
— Displays value.
If "Amp" network inputs are used for Cooling Tower Fan kW determination, then:
The voltage is ___ volts
— Enter value.
The Power Factor is __.
— Enter value.
Total Airside Fan kW
— Displays value.
If "Amp" network inputs are used for AHU VAV Fan kW determination, then:
The voltage is ___ volts
— Enter value.
The Power Factor is __.
— Enter value.
Total System kW (Ch CHWPs + CWPs + CTs + Fans)
— Displays value.
Total Building Cooling Load Tons
— Displays value.
Total System kW/ton
— Displays value.