Appendix A: The Chilled Water System Optimizer — Status only view of the Properties page
Chilled Water System Optimizer v2
CARRIER CORPORATION ©2019
Installation and Start-up Guide
53
All rights reserved
Chilled Water Temperature Optimizer Reset
Navigation:
i-Vu®
Properties
>
Control Program
>
Chilled Water Temperature Optimizer Reset
Point Name/Description
Optimizer Chilled Water Supply Reset Enable
— Displays status.
Optimized Chilled Water Supply Setpoint AV
— Displays status.
Total Chiller kW/ton
— Displays value.
Total Chilled Water Pump kW/ton
— Displays value.
Total Airside Fan kW/ton
— Displays value.
Total Chilled Water System kW/ton
— Displays value.
Section 1 - Chilled Water System Optimizer - Enable conditions
Navigation:
i-Vu®
Properties
>
Control Program
>
Chilled Water Temperature Optimizer Reset
>
Section 1 - Chilled Water System Optimizer - Enable Conditions
Point Name/Description
1. CHWS Optimizer ON Switch:
— Displays Disabled/Enabled status.
Section 2 - Automatic Overrides of Chilled Water Reset
Navigation:
i-Vu®
Properties
>
Control Program
>
Chilled Water Temperature Optimizer Reset
>
Section2 - Automatic Overrides of Chilled Water Reset
Point Name/Description
Automatic Pause & Hold of Chilled Water Reset - Status
Pause & Hold is: __
— Displays OFF/ON status.
Automatic Quick Cool Down of Chilled Water Supply - Status:
Quick Cool Down is: ___
— Displays OFF/ON status.