Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Chilled Water System Optimizer v2
CARRIER CORPORATION ©2019
Installation and Start-up Guide
67
All rights reserved
Point Name/Description
Range
New Setpoint:
___
degrees
— Displays value.
R:
degrees
Setpoint was changed?
— Enter status.
NOTE
Change setting only when
SETPOINT AVAILABLE
displays in
Operator
Instructions:
.
D:
R:
NO
NO/YES
Current Optimizer Setpoint: ___ degrees
— Displays value.
R:
degrees
Current Chiller Setpoint: ___ degrees
— Displays value.
R:
degrees
CONDENSER WATER SETPOINT - OPTIMIZATION
Optimizer Status:
— Displays status.
○
PRE-START UP
– optimizer doing pre-start calculations when first initiated.
○
FIRST RESET
– optimizer is ready for first reset.
○
CALCULATING
– optimizer is calculating next setpoint
○
NEW SETPOINT
– optimizer has new setpoint and is ready for acceptance.
○
WAITING TURN
– setpoint calculation is waiting when stagger is ON
○
PAUSE IS ON
– displays when pause is ON.
○
WARM UP IS ON
– displays when warm up is ON.
○
AUTOMATIC
– displays when in AUTOMATIC mode.
R:
OFF
PRE-START UP
FIRST RESET
CALCULATING
NEW SETPOINT
WAITING TURN
PAUSE IS ON
WARM UP IS ON
AUTOMATIC
Countdown until “New Setpoint” is determined:
Displays value
R:
(minutes:seconds)
Operator Instructions:
— Displays status.
R:
NO ACTION NEEDED
WAIT FOR RESULT
SETPOINT AVAILABLE
Elapsed time since “New Setpoint” is determined:
___ — Displays value.
R:
(minutes:seconds)
New Setpoint: ___ degrees
— Displays value.
R:
degrees
Setpoint was changed?
— Enter status.
NOTE
Change setting only when
SETPOINT AVAILABLE
displays in
Operator
Instructions:
.
D:
R:
NO
NO/YES
Current Optimizer Setpoint
: ___
degrees
— Displays value.
R:
degrees
Current Condenser Setpoint:
___
degrees
— Displays value.
R:
degrees