To set up the driver
Chilled Water System Optimizer v2
CARRIER CORPORATION ©2019
Installation and Start-up Guide
26
All rights reserved
Common and Specific Alarms
On these pages, you can enable/disable, change BACnet alarm properties, or set delays for the following BACnet
alarms:
Common alarms:
Specific alarm:
Module Halted
All Programs Stopped
Duplicate Address
Locked I/O
Control Program
Program Stopped
Excessive COV
Dead Module Timeout
Low Battery Alarm
NOTE
To set up alarm actions for controller generated alarms, see "Setting up alarm actions" in i-Vu® Help.
Module Generated Alarm
Description
Short message shown on the
Alarms
page or in an alarm action when this type of
alarm is generated.
Events
Alarm Category and Alarm
Template
See "Alarms" in i-Vu® Help.
Enable
Clear these checkboxes to disable Alarm or Return to normal messages of this
type from this controller.
Notification Class
Do not change this field.
Custom Translation Tables
You can set up a translation table that an analog input will use to translate the raw data from a non-linear sensor
to the engineering units you want it to provide on the output wire of the Analog Input microblock. In the navigation
tree, select
Custom Translation Table #1
,
#2
, or
#3
. The
Properties
page has instructions. For the input to use the
translation table, navigate to the input, select the
Details
tab, then set
Sensor Type (Scaling Method)
to
Non-
Linear, Custom Table #__
.
BACnet firewall
Requires v6-02 or later driver
If this IP controller is accessible from the Internet, you can increase security by enabling its BACnet firewall. When
enabled, this feature prevents the controller from responding to BACnet messages from unidentified sources and
allows communication only with IP addresses that you define. These can be all private IP addresses and/or a list
of IP addresses. Follow the instructions in the i-Vu® interface to set up the BACnet firewall.