300
APPENDIX B — CCN POINT TABLE (cont)
See Legend on page 307.
Configuration/BRODEFS/BROCASTS
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Activate 0=Disabled
1=Broadcast time date, Daylight Sav-
ings Time and Holiday
2=Stand alone OAT Broadcast
ccnbroad
N
N/A
OAT Broadcast
N
N/A
Bus #
Range: 0-239
Default: 0
oatbusnm
N
N/A
Element #
Range: 0-239
Default: 0
oatlocad
N
N/A
N
N/A
DAYLIGHT SAVINGS SELECT
Disable/Enable
dayl_sel
N
N/A
ENTERING
N
N/A
Month
Range: 1-12
Default: 3
startmon
N
N/A
N
N/A
Day of Week (1=Monday)
Range: 1-7
Default: 7
startdow
N
N/A
N
N/A
Week Number of Month
Range: 1-5
Default: 5
startwom
N
N/A
N
N/A
LEAVING
N
N/A
Month
Range: 1-12
Default: 10
stopmon
N
N/A
N
N/A
Day of Week (1=Monday)
Range: 1-7
Default: 7
stopdow
N
N/A
N
N/A
Week Number of Month
Range: 1-5
Default: 5
stopwom
N
N/A
N
N/A
Configuration/HOLIDAY/HOLDY_nn
(nn = 01 thru 16)
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Holiday Start Month
Range: 1-12
Default: 0
HOL-MON
N
N/A
Start Day
Range: 0-31
Default: 0
HOL-DAY
N
N/A
Duration (days)
Range: 0-99
Default: 0
HOL-LEN
N
N/A
Configuration/OCCDEFCS/OCCPC0nS
(n = 1,2)
DESCRIPTION
VALUE
UNITS
POINT NAME
TRANSLATOR
ACCESSIBLE
NETWORK
ACCESS
Timed Override Hours
0-4
hours
OVR-EXT
N
N/A
Period 1 DOW (MTWTFSSH)
DOW1
N
N/A
Occupied from
NN:NN
OCCTOD1
N
N/A
Occupied to
NN:NN
UNOCTOD1
N
N/A
Period 2 DOW (MTWTFSSH)
DOW2
N
N/A
Содержание AquaForce 30XV140
Страница 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Страница 82: ...82 Fig 81 VFD Compressor Locations 30XV225 325 30XV350 500 30XV140 325 COMPRESSOR A VFD COMPRESSOR B VFD...
Страница 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Страница 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 231: ...231 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic cont NOTE See Legend on page 226...
Страница 232: ...232 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 233: ...233 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic cont NOTE See Legend on page 226...
Страница 234: ...234 Fig 94 30XV High Tier 350 450 All Voltages Mid Tier 350 500 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 235: ...235 Fig 95 30XV Mid Tier 140 All Voltages 160 275 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 236: ...236 Fig 96 30XV High Tier 140 200 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 237: ...237 Fig 97 30XV High Tier 140 200 208 230v Mid Tier 160 200 208 230v Power Schematic NOTE See Legend on page 226...
Страница 238: ...238 Fig 98 30XV High Tier 225 325 All Voltages Mid Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 240: ...240 Fig 99 30XV Communication Wiring...
Страница 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Страница 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Страница 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Страница 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Страница 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Страница 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Страница 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Страница 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Страница 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Страница 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Страница 339: ...339 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig N Hand Off Auto This is set in Auto mode for sensorless operation...
Страница 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Страница 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Страница 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...