Chilled Water System Check
1. All chilled water valves are open.
Yes
No
2. All piping is connected properly.
Yes
No
3. All air has been purged from the system.
Yes
No
4. Chilled water pump starter controlled by chiller.
Yes
No
5. Chilled water flow switch operational.
Yes
No
6. Units installed in open loop: inlet piping to evaporator includes a 20 mesh strainer
within 10 ft of unit.
Yes
No
7. Water loop volume greater than 3 gal/ton (40 L/kW) for air conditioning
or 6 gal/ton (80 L/kW) for process cooling and low ambient operation.
Yes
No
8. Proper loop freeze protection provided to ____
F (
C).
Antifreeze type__________________ Concentration _____%.
Yes
No
(If antifreeze solution is not utilized on 30XV machines and the minimum
outdoor ambient is below 32 F (0
C), then items 10 and 11 have to be completed
to provide evaporator freeze protection to –20 F (–28.9 C). Refer to Installation
Instructions for proper evaporator winterization procedure.)
9. Outdoor piping wrapped with electric heater tape.
Yes
No
10. Evaporator heaters and oil separator heaters installed and operational.
Yes
No
11. Is the Unit equipped with low ambient head pressure control?
Yes
No
a. If yes, are wind baffles installed?
Yes
No
C. UNIT START-UP
1. All liquid line service valves are open.
Yes
No
2. Verify actuated ball valve (ABV) operation.
Yes
No
3. All suction and discharge service valves are open.
Yes
No
4. Economizer service valves open. (Leaving Main EXV and
Leaving Brazed Plate Heat Exchanger [Economizer])
Yes
No
5. Oil service valves open.
Yes
No
6. Leak check unit. Locate, repair and report any refrigerant leaks.
Yes
No
7. Voltage at terminal block is within unit nameplate range.
Yes
No
Check voltage imbalance: A-B______ A-C______B-C______
Average voltage = __________ (A-B + A-C + B-C)/3
Maximum deviation from average voltage = _______
Voltage imbalance = ______% (max. deviation / average voltage) X 100
Is voltage imbalance less than 2%.
Yes
No
(DO NOT start chiller if voltage imbalance is greater than 2%.
Contact local utility for assistance.)
8. Verify evaporator flow rate
Pressure entering evaporator _____ psig (kPa)
Pressure leaving evaporator _____ psig (kPa)
Evaporator pressure drop _____ psig (kPa)
Psig x 2.31 ft/psi = _____ ft of water
kPa x 0.334 m/psi = _____ mm of water
Evaporator flow rate _____ gpm (L/s) (See Evaporator Pressure Drop Curve)
Start and Operate Machine
1. Complete component test utilizing Quick Test Mode
2. Operate all condenser fans and verify operation and rotation.
3. Operate compressors using manual test mode.
4. Check refrigerant and oil charge. Record charge information.
5. Record compressor and condenser fan motor current.
6. Record operating data.
7. Provide operating instructions to owner’s personnel.
Содержание AquaForce 30XV140
Страница 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Страница 82: ...82 Fig 81 VFD Compressor Locations 30XV225 325 30XV350 500 30XV140 325 COMPRESSOR A VFD COMPRESSOR B VFD...
Страница 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Страница 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 231: ...231 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic cont NOTE See Legend on page 226...
Страница 232: ...232 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 233: ...233 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic cont NOTE See Legend on page 226...
Страница 234: ...234 Fig 94 30XV High Tier 350 450 All Voltages Mid Tier 350 500 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 235: ...235 Fig 95 30XV Mid Tier 140 All Voltages 160 275 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 236: ...236 Fig 96 30XV High Tier 140 200 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 237: ...237 Fig 97 30XV High Tier 140 200 208 230v Mid Tier 160 200 208 230v Power Schematic NOTE See Legend on page 226...
Страница 238: ...238 Fig 98 30XV High Tier 225 325 All Voltages Mid Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 240: ...240 Fig 99 30XV Communication Wiring...
Страница 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Страница 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Страница 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Страница 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Страница 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Страница 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Страница 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Страница 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Страница 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Страница 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Страница 339: ...339 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig N Hand Off Auto This is set in Auto mode for sensorless operation...
Страница 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Страница 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Страница 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...