218
39203
Fan A2 VFD
Error, Circuit A
The Variable Frequency Drive (VFD)
has detected a missing motor and
generated a W203 Missing Motor
Warning. Motor curve parameters are
loaded to the fan VFD from the unit
controls so that a motor current can be
determined. If the current measured
does not correspond to the motor
curve amp draw for the given speed.
The unit controls will not generate the
alert until one of the following condi-
tions is met: 1. The Outdoor Ambient
Temperature is equal to or greater
than 50°F (10°C) and the VFD reports
the W203 Missing Motor Warning for
at least 30 seconds 2. The Outdoor
Ambient Temperature is less than
50°F (10°C) and the VFD reports the
W203 Missing Motor Warning for at
least 5 minutes
None; warning only
Automatic
Check motor connections to the VFD; check
harness connections to the motor; confirm unit
configuration
41nnn
Fan B1 VFD
Error, Circuit B
Fan B1 VFD Circuit B fault (see VFD
Alarms and Alerts section on
page 220)
No action unless
subcode =
013: over current
204: locked rotor
in which case circuit
will shut down
Automatic; reset is manual
for subcode 013 and 204
See Table 171 for VFD Alarm/Alert Codes
41203
Fan B1 VFD
Error, Circuit B
The Variable Frequency Drive (VFD)
has detected a missing motor and
generated a W203 Missing Motor
Warning. Motor curve parameters are
loaded to the fan VFD from the unit
controls so that a motor current can be
determined. If the current measured
does not correspond to the motor
curve amp draw for the given speed.
The unit controls will not generate the
alert until one of the following condi-
tions is met: 1. The Outdoor Ambient
Temperature is equal to or greater
than 50°F (10°C) and the VFD reports
the W203 Missing Motor Warning for
at least 30 seconds 2. The Outdoor
Ambient Temperature is less than
50°F (10°C) and the VFD reports the
W203 Missing Motor Warning for at
least 5 minutes
None; warning only
Automatic
Check motor connections to the VFD; check
harness connections to the motor; confirm unit
configuration
42nnn
Fan B2 VFD
Error, Circuit B
Fan B2 VFD Circuit B fault (see VFD
Alarms and Alerts section on
page 220)
No action unless
subcode =
013: over current
204: locked rotor
in which case circuit
will shut down
Automatic; reset is manual
for subcode 013 and 204
See Table 171 for VFD Alarm/Alert Codes
42203
Fan B2 VFD
Error, Circuit B
The Variable Frequency Drive (VFD)
has detected a missing motor and
generated a W203 Missing Motor
Warning. Motor curve parameters are
loaded to the fan VFD from the unit
controls so that a motor current can be
determined. If the current measured
does not correspond to the motor
curve amp draw for the given speed.
The unit controls will not generate the
alert until one of the following condi-
tions is met: 1. The Outdoor Ambient
Temperature is equal to or greater
than 50°F (10°C) and the VFD reports
the W203 Missing Motor Warning for
at least 30 seconds 2. The Outdoor
Ambient Temperature is less than
50°F (10°C) and the VFD reports the
W203 Missing Motor Warning for at
least 5 minutes
None; warning only
Automatic
Check motor connections to the VFD; check
harness connections to the motor; confirm unit
configuration
04502
Loss of Communi-
cation with Auxil-
iary Board A
Alarm will trip if communication with
AUX Board A is lost
Circuit A will be shut
down immediately
Automatic when the commu-
nication is reestablished
If this condition is encountered, check the fol-
lowing items for faults:
•
power supply to the Aux board
•
local equipment network (LEN) wiring
04503
Loss of Communi-
cation with Auxil-
iary Board B
Alarm will trip if communication with
AUX Board B is lost
Circuit B will be shut
down immediately
Automatic when the commu-
nication is reestablished
04603
Loss of communi-
cation with Energy
Management
Board
Alarm will trip if communication with
Energy Management Module (EMM)
Board is lost
No action on the unit,
EMM functions will
not operate
Automatic when the commu-
nication is reestablished
If this condition is encountered, check the fol-
lowing items for faults:
•
the EMM is installed (
Main Menu
Con-
figuration Menu
Factory Parameters
Line 9 Energy Management Module
=
Yes)
•
power supply to EMM
•
address of the EMM
•
local equipment network (LEN) wiring
If no EMM board is installed:
•
confirm unit configuration to be sure that
no options requiring EMM are selected
Table 168 — Alarm Details by Code (cont)
ALARM
CODE
ALARM NAME
CRITERIA
FOR TRIP
ACTION TAKEN
BY CONTROL
RESET
METHOD
POSSIBLE CAUSES/CORRECTIVE ACTIONS
Содержание AquaForce 30XV140
Страница 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Страница 82: ...82 Fig 81 VFD Compressor Locations 30XV225 325 30XV350 500 30XV140 325 COMPRESSOR A VFD COMPRESSOR B VFD...
Страница 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Страница 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 231: ...231 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic cont NOTE See Legend on page 226...
Страница 232: ...232 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 233: ...233 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic cont NOTE See Legend on page 226...
Страница 234: ...234 Fig 94 30XV High Tier 350 450 All Voltages Mid Tier 350 500 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 235: ...235 Fig 95 30XV Mid Tier 140 All Voltages 160 275 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 236: ...236 Fig 96 30XV High Tier 140 200 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 237: ...237 Fig 97 30XV High Tier 140 200 208 230v Mid Tier 160 200 208 230v Power Schematic NOTE See Legend on page 226...
Страница 238: ...238 Fig 98 30XV High Tier 225 325 All Voltages Mid Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 240: ...240 Fig 99 30XV Communication Wiring...
Страница 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Страница 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Страница 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Страница 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Страница 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Страница 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Страница 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Страница 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Страница 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Страница 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Страница 339: ...339 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig N Hand Off Auto This is set in Auto mode for sensorless operation...
Страница 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Страница 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Страница 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...