Fig. 82 — Typical Fan VFD Location
VFD DISPLAY NAVIGATION
NOTE: The following instructions apply to the Danfoss VLT
VFD.
The VFD can be operated in 2 ways:
• Graphical Local Control Panel (GLCP)
• RS-485 serial communication for PC connection
Graphical Local Control Panel
The LCD display is divided into 4 functional groups:
1. Graphical display with Status lines
2. Menu keys and indicator lights (LEDs) — selecting mode,
changing parameters and switching between display func-
tions
3. Navigation keys and indicator lights (LEDs)
4. Operation keys and indicator lights (LEDs)
See Fig. 83. The display is backlit with a total of 6 alpha-nu-
meric lines. All data is displayed on the GLCP, which can show
up to 5 operating variables while in Status mode.
The display lines (see items a-c in Fig. 83) function as follows:
a. The status line at the top of the display shows VFD
status when in [Status] mode or up to 2 variables
when not in [Status] mode, or in case of an alarm or
warning (alert).
b. The operator data line in the middle section shows up
to 5 variables with their related units, regardless of
status. In the case of an alarm or warning, the warning
is shown instead of the variables.
c. The status line in the bottom section always shows the
state of the VFD in Status mode.
The operator can toggle among 3 status read-out screens by
touching the Status key. Several values or measurements can
be linked to each of the displayed operating variables. The val-
ues/measurements to be displayed can be defined via parame-
ter 0-20 Display Line 1.1 Small, 0-21 Display Line 1.2 Small,
0-22 Display Line 1.3 Small, 0-23 Display Line 2 Large and 0-
24 Display Line 3 Large. The settings are accessed by selecting
QUICK MENU
Q3 Function Setups
Q3-1 General Set-
tings
Q3-13 Display Settings
. Each value/measurement
readout parameter selected in 0-20 Display Line 1.1 Small to
0-24 Display Line 3 Large has its own scale and number of
digits after a possible decimal point. Larger numeric values are
displayed with fewer digits after the decimal point. For exam-
ple, a current readout might be 5.25 A,15.2 A, or 105 A.
Status Display I is standard after start-up or initialization.
Touch [INFO] to obtain information about the value/measure-
ment linked to the displayed operating variables 1.1, 1.2, 1.3,
2, and 3). See the operating variables shown in the display in
Fig. 84. Variables 1.1, 1.2, and 1.3 are shown in small size.
Variables 2 and 3 are shown in medium size.
Fig. 83 — VFD Graphical Local Control Panel
Fan VFD A1
Fan VFD B2
Fan VFD B1
Fan VFD A2
IMPORTANT: The VFDs are configured through the
Carrier Controller controls, and parameters should not be
changed manually. This section is included for informa-
tion and troubleshooting purposes only.
a
b
c
1
2
3
4
a30-5862
LEGEND
1 —
Graphical display with status lines
2 —
Menu keys and indicator lights
3 —
Navigation keys and indicator lights
4 —
Operation keys and indicator lights
a —
Status line
b —
Operator data lines
c —
Status messages
Содержание AquaForce 30XV140
Страница 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Страница 82: ...82 Fig 81 VFD Compressor Locations 30XV225 325 30XV350 500 30XV140 325 COMPRESSOR A VFD COMPRESSOR B VFD...
Страница 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Страница 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 231: ...231 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic cont NOTE See Legend on page 226...
Страница 232: ...232 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 233: ...233 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic cont NOTE See Legend on page 226...
Страница 234: ...234 Fig 94 30XV High Tier 350 450 All Voltages Mid Tier 350 500 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 235: ...235 Fig 95 30XV Mid Tier 140 All Voltages 160 275 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 236: ...236 Fig 96 30XV High Tier 140 200 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 237: ...237 Fig 97 30XV High Tier 140 200 208 230v Mid Tier 160 200 208 230v Power Schematic NOTE See Legend on page 226...
Страница 238: ...238 Fig 98 30XV High Tier 225 325 All Voltages Mid Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 240: ...240 Fig 99 30XV Communication Wiring...
Страница 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Страница 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Страница 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Страница 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Страница 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Страница 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Страница 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Страница 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Страница 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Страница 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Страница 339: ...339 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig N Hand Off Auto This is set in Auto mode for sensorless operation...
Страница 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Страница 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Страница 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...