6.1 - Operating range
30XB & 30XBP
Evaporator leaving water temperature, °C
Entering air temperature, °C
30XB & 30XBP with option 15LS
Evaporator leaving water temperature, °C
Entering air temperature, °C
Legend:
Operating range, unit equipped with option 28 (winter operation).
Below 0 °C air temperature the unit must either be equipped with the
evaporator frost protection option (41A or 41B), or the water loop must
be protected against frost by using a frost protection solution (by the
installer).
Part load average
ATTENTION: Option 28 (Winter operation)
If the outside temperature is below -10 °C and the unit has
been switched off for more than 4 hours, it is necessary to
wait 2 hours after the unit has been switched on again to allow
the frequency converter to warm up.
Water heat exchanger
Minimum
Maximun
Entering temperature at start-up
°C
-
45(1)
Leaving temperature during operation
°C
3,3
15
Entering/leaving water temperature difference
K
2,8
10
Condenser air temperature
Minimum
Maximun
Storage
-20
68
Operation, standard unit
-10
55(2)
With winter operation option (option 28)
-20
55(2)
With Low noise option (option 15LS)
-10
52(2)
Note: If the air temperature is below 0°C, a glycol/water solution or the frost protection
option must be used.
Note: If the leaving water temperature is below 4°C, a glycol/water solution or the
frost protection option must be used.
(1)
Based on the installation type and the air temperature
(2)
Part load, depended of sizes & leaving water temperature
6.2 - Minimum chilled water flow (units without
hydraulic module)
The minimum chilled water flow is shown in the table on the next
page. If the system flow is less than this, the evaporator flow can
be recirculated, as shown in the diagram.
For minimum chilled water flow rate
1
2
1 Evaporator
2 Recirculation
6.3 - Maximum chilled water flow (units without
hydraulic module)
The maximum chilled water flow is shown in the table on the next
page. If the system flow exceeds the maximum value, it can be
bypassed as shown in the diagram.
For maximum chilled water flow rate
1
2
1 Evaporator
2 Bypass