4.5 - Electrical data (continued)
30XB from 1100 to 1700 with option 254 or 255 (continued)
30XB with option 254 or 255
1100
1200
1300
1400
1500
1550
1700
Maximum current (Un-10%)
(1)
Standard unit
Circuit 1
(a)
A
319
366
440
470
509
740
593
Circuit 2
(a)
A
464
509
470
505
509
370
593
Option 081
A
785
877
912
977
1020
1113
Unit + option 15LS
Circuit 1
(a)
A
309
357
424
454
491
727
574
Circuit 2
(a)
A
452
493
454
489
491
357
574
Option 081
A
762
850
880
945
985
1074
Nominal start-up current
(3)
Standard unit
Circuit 1
(a)
A
590
587
629
629
629
954
812
Circuit 2
(a)
A
635
629
629
629
629
477
812
Option 081
A
949
986
985
1015
1019
1316
Option 081 & Opt 25c
A
811
820
844
862
862
Unit + option 15LS
Circuit 1
(a)
A
576
578
613
613
611
941
793
Circuit 2
(a)
A
615
613
613
613
611
464
793
Option 081
A
1020
1070
1063
1098
1099
1393
Option 081 & Opt 25c
A
776
795
812
830
826
Maximum start-up current(Un)
(2)
Standard unit
Circuit 1
(a)
A
590
590
629
629
629
954
812
Circuit 2
(a)
A
635
632
629
629
629
477
812
Option 081
A
1055
1101
1095
1130
1134
1431
Option 081 & Opt 25c
A
811
820
844
862
862
Unit + option 15LS
Circuit 1
(a)
A
576
578
613
613
611
941
793
Circuit 2
(a)
A
615
613
613
613
611
464
793
Option 081
A
1020
1070
1063
1098
1099
1393
Option 081 & Opt 25c
A
776
795
812
830
826
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XB1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.
4.6 - Compressor electrical data
Compressor
I Nom
(1)
I Max
(Un)
(2)
I Max
(Un - 10%)
(3)
LRYA
A
(4)
LRDA
A
(5)
Cos
Phi nom.
(6)
Cos
Phi Max.
(7)
06TSA155
64
93
99
170
530
0,87
0,9
06TSA186
80
111
118
170
530
0,86
0,89
06TTA266
117
162
172
303
945
0,86
0,9
06TTA301
132
177
188
388
1210
0,87
0,9
06TTA356
153
207
220
388
1210
0,87
0,9
06TUA483
225
292
311
587
1828
0,87
0,88
06TUA554
241
338
360
587
1828
0,88
0,89
06TVA680
302
400
436
629
1919
0,87
0,89
06TVA753
315
430
468
629
1919
0,88
0,89
06TVA819
347
465
496
629
1919
0,88
0,89
Legend
(1) Nominal current draw at standard Eurovent conditions (see definition of conditions under nominal unit current draw)
(2) Maximum operating current
(3) Maximum compressor operating current, limited by the unit (current given for maximum capacity at 360 V)
(4) Locked rotor current for star connection (connection during compressor start-up)
(5) Locked rotor current for delta connection
(6) Value at standard Eurovent conditions: evaporator entering/leaving water temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C.
(7) Value at maximum capacity and nominal voltage
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS